Phoenix AXL F RTD4 XC 1H-Temperature Module 1035430,Axioline F, Temperature Recording Module, Analog Input: 4 (for Thermal Resistance Temperature Detector), Connection Technology: 2, 3, 4 Wire (Shielding), Local Bus Transmission Rate: 100 Mbps, Extreme Environment Model, Protection Level: IP20, Including Bus Base Module and Axioline F Connector
width
35mm
height
126.1mm
depth
54mm
Notes on dimensional data
using TH 35-7.5 rails (as EN60715).
Application Description
Application Description
for industrial applications only
Axioline F Local Bus
interfaces
2
Connection Mode
Bus Base Module
transmission speed
100 Mbps
Module
Input Address Area
8 Byte
Output Address Area
0 Byte
the required parameter data
12 Byte
6 Byte
simulation
Enter Name
Analog Input
Input Description
Input for Resistance Temperature Sensor
Input Quantity
4 (for RTD)
Connection Mode
in-line connection
connection system
2, 3, 4 wire (shielded)
A/D Converter Resolution
24.
Available Sensor Types (RTDs)
Pt, Ni, KTY, Cu sensors
data format
IB IL,S7 compatible
measurement value expression
16 bits (15 bits + sign bit)
input filter time
40 ms
60 ms
100 ms
120 ms (settable)
current power supply rating
1 mA (Pt 100,Ni 100, RLin500 Ω; pulse current, the specification is valid at the sampling stage)
210 µA (Pt 1000,Ni 1000,RLin5000 Ω; pulse current, the specification is valid at the sampling stage)
difference non-linearity
Typical 1 ppm / ± 0.0001 % (in all series)
integrated non-linearity
Typical 30 ppm / ± 0.003 % (Pt 100)
typical 20 ppm / ± 0.002 % (RLin500 Ω)
typical 200 ppm / ± 0.02 % (RLin5000 Ω)
Linear resistance measuring range
0 Ω ... 500 Ω
0 kΩ ... 5 kΩ
protection circuit
Short circuit protection for input, overload protection
input
Sensor Power Supply
2688310