Phoenix AXL F SSDO8/3 1F-Security module 2702264,Axioline F, digital output module, functional safety, SafetyBridge technology, digital output: 4 (for dual-channel distribution),8 (for single-channel distribution),2 A, Connection technology: 2,3 wires, protection level: IP20
| width |
53.6mm |
| height |
126.1mm |
| depth |
54mm |
| Notes on dimensional data |
Shell Size |
| Application Description |
| Application Description |
for industrial applications only |
| Axioline F Local Bus |
| Channels |
1 |
| Connection Mode |
bus base module |
| Module |
| Input Address Area |
8 Byte |
| Output Address Area |
8 Byte |
| the required parameter data |
1 Byte |
|
7 Byte |
| digital quantity: |
| Output Name |
Digital Output |
| Connection Mode |
in-line |
| connection system |
2,3 lines |
| outputs |
4 (for dual channel distribution) |
| 8 (for single channel distribution) |
| 8 |
| protection circuit |
Provide overload protection for free-wheeling diode circuits for inductive loads, discharge circuits for accelerated discharge of capacitive loads |
| output voltage |
24V DC |
| output current |
max. 2 A (per channel) |
| maximum 1.5 A (per channel, per CULUS) |
| max. 4 A (per group) |
| max 3 A (per group, according to CULUS) |
| Maximum 8 A (total current of all outputs; please follow the precautions in the user manual.) |
| Max. 6 A (total current of all outputs, according to CULUS) |
| the maximum output current per channel |
2 A |
| maximum output current per module/terminal |
8 A |
| overload behavior |
affected output is disabled and a diagnostic message is generated. |