Phoenix AXL SE IOL4-Communication module 1088132,Axioline Smart Elements,IO-Link master station, IO-Link port category A: 4, wiring mode: in-line connection, connection technology: 3 wires, protection level: IP20

width 14.9mm
height 62.2mm
depth 62mm

Application Description
Application Description for industrial applications only

Smart Element Interface
interfaces 1
Connection Mode Card Edge Connector
transmission speed See Systems Using Smart Element.
to ready < 500 ms

Module
Hex ID Encoding None
Process Data Channel 512 bit
Input Address Area 64 Byte
Output Address Area 64 Byte

digital quantity
Input Description IO-Link port in digital input (DI) mode
Input Quantity max. 4 (EN 61131-2 Type 1)
Connection Mode in-line connection
connection system 3 lines
Rated input voltage UIN 24V DC
input voltage range, "0" signal -0.3V DC ... 5V DC
input voltage range, "1" signal 11V DC ... 30V DC
Rated input current Typical 2.5 mA
sensor current per channel Maximum 500 mA (off L /L-)
input filter time 1 &micro;s
IO-Link
ports 4
Connection Mode in-line connection
connection system 3 lines
Port Type Class A
1088132

Phoenix AXL SE IOL4-Communication Module 1088132

Product Center