Phoenix TRIO3-PS/3AC/24DC/10-power supply 1159042, primary switching power supply, TRIO POWER, in-line connection, DIN rail installation, input: 3 phases, output: 24V DC / 10 A, adjustable range 24V DC ... 28V DC

AC operation
Power System Configuration star network (TN,TT,IT (PE))
Rated input voltage range 3x 400V AC ... 500V AC
Input Voltage Range 3x 400V AC ... 500V AC -20 % ... +10%
2x 400V AC ... 500V AC ±10%
National Grid Typical Voltage 3x 400V AC
3x 480V AC
Supply Voltage AC
Impulse current < 13 A (25 °C)
impulse current integral (I2t) < 0.25 A2s
frequency range (fN) 50Hz ... 60Hz ± 10%
grid buffer time Typical 35 ms (3x 400V AC)
Typical 58 ms (3x 480V AC)
power consumption 3x 0.59 A (3x 400V AC)
3x 0.46 A (3x 500V AC)
2x 1.15 A (2x 400V AC)
2x 0.86 A (2x 500V AC)
protection circuit transient protection; varistor
power factor (cos phi) 0.57 (3x 480V AC)
Device Power Fuse 3.15 A built-in (device protection)
recommend use 3x 3 A ... 16 A (characteristics B, C, D, K or similar)
PE discharge current < 3.5 mA

efficiency Typical 92.3 % (3x 400V AC)
Typical 92.4 % (3x 480V AC)
Rated output voltage 24V DC
output voltage (USet) setting range 24V DC ... 28V DC (> 24V DC, stable capacity limit)
Rated output current (IN) 10 A
Dynamic Boost (IDyn.Boost) max. 15 A (5 s)
Short-circuit protection is
Anti-aircraft turn is
Attenuation 60°C ... 70°C
amplitude factor Typical 2.77 (3x 400V AC)
Typical 2.94 (3x 480V AC)
output power (PN) 240W
output power (Pdynamic margin) maximum 360W (5 s)
and connect , the use of diodes allows for increased power and increased redundancy
Concatenation Yes, for higher output voltages (in compliance with SELV limits)
feedback voltage resistance ≤ 35V DC
output ≤ 35V DC
residual wave 10 mV typicalSS(rated value)
control deviation <1% (load change, static 10%... 90%)
<3% (load change, dynamic 10%... 90%)
< 0.1 % (input voltage variation is ± 10 %)