Phoenix TRIO-PS-2G/1AC/12DC/10-power supply 2903158, using in-line connection TRIO POWER power supply, suitable for DIN rail installation, primary switching mode, input: single phase, output: 12V DC/10 A
AC operation
Network Type
star network
Rated input voltage range
100V AC ... 240V AC
Input Voltage Range
100V AC ... 240V AC -15 % ... +10%
AC input voltage range
85V AC ... 264V AC
maximum dielectric strength
≤ 300V AC 15 s
National Grid Typical Voltage
120V AC
230V AC
Supply Voltage
AC/DC
Impulse current
≤ 30 A (typical)
impulse current integral (I2t)
< 1.5 A2s
Surge current limit
Typical 30 A (after 1 ms)
AC frequency range
50Hz ... 60Hz ± 10%
grid buffer time
Typical 20 ms (120V AC)
Typical 20 ms (230V AC)
power consumption
2.2 A (100V AC)
1.9 A (120V AC)
1.1 A (230V AC)
1.1 A (240V AC)
Rated power consumption
254.7 VA
protection circuit
transient surge protection; varistor
power factor (cos phi)
0.53
Typical Response Time
< 1 s
input fuse
6.3 A fast fuse (built-in (equipment protection))
recommend use
6 A ... 16 A (characteristics B, C, D, K)
PE discharge current
< 0.25 mA
DC operation
Rated input voltage range
122V DC ... 250V DC
Input Voltage Range
122V DC ... 275V DC
operation
> 106V AC
Attenuation
< 99V DC (2 %/V)
Shutdown Voltage
105V DC
Supply Voltage
AC/DC
grid buffer time
> 100 ms (230V AC)
power consumption
1.4 A (122V DC)
0.6 A (250V DC)
efficiency
Typical 87.5 % (120V AC)
Typical 88.7 % (230V AC)
output characteristics
U/ I with dynamic load reserve
Rated output voltage
12V DC ±1%
output voltage (USet) setting range
12V DC ... 18V DC (> 12V DC, limited stable capacity)