Phoenix TRIO-PS-2G/1AC/12DC/5/C2LPS-power supply 2903157, TRIO POWER power supply with in-line connection, suitable for DIN rail installation, primary switch mode, input: single phase, output: 12V DC/5 A C2LPS

AC operation
Network Type star network
Rated input voltage range 100V AC ... 240V AC
Input Voltage Range 100V AC ... 240V AC -15 % ... +10%
AC input voltage range 85V AC ... 264V AC
maximum dielectric strength ≤ 300V AC 15 s
National Grid Typical Voltage 120V AC
230V AC
Supply Voltage AC/DC
Impulse current ≤ 25 A (typical)
impulse current integral (I2t) < 0.6 A2s
Surge current limit Typical 25 A (after 1 ms)
AC frequency range 50Hz ... 60Hz ± 10%
grid buffer time Typical 20 ms (120V AC)
Typical 110 ms (230V AC)
power consumption 1.1 A (100V AC)
1 A (120V AC)
0.6 A (230V AC)
0.6 A (240V AC)
Rated power consumption 137.3 VA
protection circuit transient surge protection; varistor
power factor (cos phi) 0.51
Typical Response Time < 1 s
input fuse 6.3 A slow fuse
recommend use 6 A ... 16 A (characteristics B, C, D, K)
PE discharge current < 0.25 mA
DC operation
Rated input voltage range 110V DC ... 250V DC
Input Voltage Range 99V DC ... 275V DC
turn-on voltage ≥ 85V DC
Shutdown Voltage < 80V DC
Supply Voltage AC/DC
power consumption 0.7 A (110V DC)
0.3 A (250V DC)

efficiency > 86% (230V AC and rated)
output characteristics U/ I with dynamic load reserve
Rated output voltage 12V DC ±1%
output voltage (USet) setting range 12V DC ... 18V DC (> 12V DC, limited stable capacity)
Rated output current (IN) 5 A
Attenuation > 60°C ... 70°C (2.5 %/K)
feedback voltage resistance < 25V
output ≤ 22V DC
control deviation <1% (load change, static 10%... 90%)
<3% (dynamic load change 10%... 90%, 10Hz)
< 0.1 % (input voltage variation is ± 10 %)
2903147

Phoenix TRIO-PS-2G/1AC/12DC/5/C2LPS-Power 2903157

Product Center