Phoenix TRIO-PS-2G/1AC/24DC/10/B + D-power supply 2903145, TRIO POWER switching power supply with in-line connection, suitable for DIN rail installation, single-phase input, output: 24V DC/10 A
| AC operation | |
| Network Type | star network |
| Rated input voltage range | 100V AC ... 240V AC |
| Input Voltage Range | 100V AC ... 240V AC -15 % ... +10% |
| turn-on voltage | > 75V AC |
| Shutdown Voltage | < 70V AC |
| maximum dielectric strength | 300V AC 15 s |
| National Grid Typical Voltage | 120V AC |
| 230V AC | |
| the voltage type of the supply voltage | AC/DC |
| Impulse current | Typical 20 A |
| impulse current integral (I2t) | < 0.5 A2s |
| Surge current limit | Typical 20 A (after 1 ms) |
| AC frequency range | 50Hz ... 60Hz ± 5Hz |
| frequency range (fN) | 50Hz ... 60Hz ± 10% |
| grid buffer time | Typical 20 ms (120V AC) |
| Typical 20 ms (230V AC) | |
| power consumption | 3.1 A (100V AC) |
| 2.4 A (120V AC) | |
| 1.3 A (230V AC) | |
| 1.4 A (240V AC) | |
| Rated power consumption | 285 VA |
| protection circuit | transient surge protection; varistor |
| power factor (cos phi) | 0.93 |
| Typical Response Time | < 1 s |
| input fuse | 6.3 A (built-in (equipment protection)) |
| recommend use | 6 A ... 16 A (characteristics B, C, D, K) |
| PE discharge current | < 3.5 mA |
| 0.8 mA (264V AC,60 Hz) | |
| Power factor | > 0.9 (120V AC) |
| > 0.8 (230V AC) | |
| DC operation | |
| Rated input voltage range | 110V DC ... 250V DC |
| Input Voltage Range | 110V DC ... 250V DC -10 % ... +10% |
| operation | 88V DC ... 99V DC (attenuation <99V DC: 2.5 %/V) |
| Attenuation | < 99V DC (2 %/V) |
| turn-on voltage | ≥ 95V DC |
| Shutdown Voltage | < 70V DC |
| the voltage type of the supply voltage | AC/DC |
| grid buffer time | > 15 ms (230V AC) |
| power consumption | 2.5 A (110V DC) |
| 1.1 A (250V DC) | |