Phoenix TRIO-PS-2G/1AC/48DC/10-power supply 2903160, TRIO POWER switching power supply with in-line connection, suitable for DIN rail installation, single-phase input, output: 48V DC/10 A

AC operation
Network Type star network
Rated input voltage range 100V AC ... 240V AC
Input Voltage Range 100V AC ... 240V AC -15 % ... +10%
maximum dielectric strength ≤ 300V AC 15 s
National Grid Typical Voltage 120V AC
230V AC
Supply Voltage AC/DC
Impulse current 20 A (at 25°C)
impulse current integral (I2t) < 0.7 A2s
Surge current limit Typical 20 A (after 1 ms)
AC frequency range 50Hz ... 60Hz ± 10%
grid buffer time Typical 10 ms (120V AC)
Typical 15 ms (230V AC)
power consumption 5.6 A (100V AC)
5.4 A (120V AC)
2.6 A (230V AC)
2.4 A (240V AC)
Rated power consumption 604.7 VA
protection circuit transient surge protection; varistor
power factor (cos phi) 0.85
Typical Response Time < 1 s
input fuse 10 A (built-in (equipment protection))
recommend use 10 A ... 16 A (characteristics B, C, D, K)
PE discharge current < 3.5 mA
DC operation
Rated input voltage range 110V DC ... 250V DC
Input Voltage Range 99V DC ... 275V DC
turn-on voltage ≥ 93V DC
Shutdown Voltage < 85V DC
Supply Voltage AC/DC
grid buffer time > 20 ms (230V AC)
power consumption 5 A (110V DC)
2.2 A (250V DC)

efficiency > 93% (230V AC and rated)
output characteristics U/ I with dynamic load reserve
Rated output voltage 48V DC ±1%
output voltage (USet) setting range 36V DC ... 55V DC (> 48V DC, limited stable capacity)
Rated output current (IN) 10 A
Dynamic Boost (IDyn.Boost) 15 A (5 s)
Attenuation > 60°C ... 70°C (2.5 %/K)
feedback voltage resistance ≤ 60V DC
output ≤ 60V DC
control deviation <1% (load change, static 10%... 90%)
<3% (dynamic load change 10%... 90%, 10Hz)
< 0.1 % (input voltage variation is ± 10 %)
2903155

Phoenix TRIO-PS-2G/1AC/48DC/10-Power 2903160