Phoenix TRIO-PS-2G/1AC/48DC/5-power supply 2903159, TRIO switching power supply suitable for DIN rail installation, input: single phase, output: 48V DC/5 A, dynamic power margin, tool-free quick connection Technology, used to connect rigid wires and flexible wires with cold press head
AC operation
Network Type
star network
Rated input voltage range
100V AC ... 240V AC
Input Voltage Range
100V AC ... 240V AC -15 % ... +10%
maximum dielectric strength
≤ 300V AC 15 s
National Grid Typical Voltage
120V AC
230V AC
Supply Voltage
AC/DC
impulse current integral (I2t)
< 0.3 A2s
Surge current limit
15 A (after 1 ms)
AC frequency range
50Hz ... 60Hz ± 10%
frequency range (fN)
50Hz ... 60Hz ± 5Hz
grid buffer time
Typical 15 ms (120V AC)
Typical 15 ms (230V AC)
power consumption
2.9 A (100V AC)
2.3 A (120V AC)
1.2 A (230V AC)
1.2 A (240V AC)
Rated power consumption
285.7 VA
protection circuit
transient surge protection; varistor
power factor (cos phi)
0.91
input fuse
6.3 A (built-in (equipment protection))
recommend use
6 A ... 16 A (characteristics B, C, D, K)
PE discharge current
< 3.5 mA
< 1.7 mA (264V AC,60 Hz)
Power factor
> 0.9 (120V AC)
> 0.9 (230V AC)
DC operation
Rated input voltage range
110V DC ... 250V DC
Input Voltage Range
110V DC ... 250V DC ±10%
operation
> 88V DC (attenuation <99V DC: 2%/V)
Attenuation
< 99V DC (2 %/V)
turn-on voltage
90V DC
Shutdown Voltage
70V DC
Supply Voltage
AC/DC
grid buffer time
> 20 ms (230V AC)
power consumption
2.5 A (110V DC)
1.1 A (250V DC)
efficiency
Typical 90.5 % (120V AC)
Typical 91% (230V AC)
output characteristics
U/ I with dynamic load reserve
Rated output voltage
48V DC ±1%
output voltage (USet) setting range
36V DC ... 55V DC (> 48V DC, limited stable capacity)