Phoenix TRIO-UPS-2G/1AC/24DC/10-uninterruptible power supply 2907161,TRIO UPS-uninterruptible power supply with integrated high-power storage device, USB (Modbus/RTU), DIN rail installation, in-line connection, input: 1 Phase, output: 24V DC/10 A
Input Voltage Range
100V AC ... 240V AC -15 % ... +10%
Supply Voltage
AC
Impulse current
< 9 A
impulse current integral (I2t)
< 0.2 A2s
frequency range (fN)
50Hz ... 60Hz (± 10%)
grid buffer time
≥ 25 ms (120V AC)
Suction time
Typical 200 ms
Typical current consumption
4.5 A (100V AC)
input fuse
6.3 A (slow fuse, internal)
signal Bat.-Start
Wiring Identification
3.6
signal distribution
Bat.-Start
low signal
connected to SGnd < 2.7 kΩ
High Signal
ON (> 200 kΩ between battery boot and SNew)
signal Remote
Wiring Identification
3.5
signal distribution
Remote
low signal
connected to SGnd < 2.7 kΩ
High Signal
ON (> 35 kΩ between remote and SGnd)
efficiency
90% typical (120V AC)
Typical 91% (230V AC)
Typical 96% (battery operated)
Attenuation
> 60°C (POutrating/K)
amplitude factor
1.5 (120V AC)
1.5 (230V AC)
switching time
< 20 ms
USB Parallel Connection
yes, the diode modules are decoupled
UPS series connection
No
Parallel Power Storage Device
is
feedback voltage resistance
≤ 35V DC
output
< 30V DC
residual wave
< 20 mV
control deviation
< 0.55 % (load change, static 10%... 90%)
< 2.6 % (dynamic load change 10%... 90%, 10Hz)
< 0.05 % (input voltage variation is ± 10 %)
rise time
< 30 ms
Allowable Spare Fuses
B10
mains power supply
output voltage
24V DC
Output Voltage Range
24V DC ... 28V DC (> 24V continuous capacity)
Output current IN
10 A
dynamic power margin (IDyn.Boost)
15 A
Output power POUT(UN,IOUT= IN)
240W
maximum no-load power consumption
< 3W (230V AC)
Maximum rated load power loss
< 32W (230V AC)
battery operation
output voltage
UBAT-0.1V DC
Output Voltage Range
18V DC ... 30V DC
Output current IN
10 A
dynamic power margin (IDyn.Boost)
15 A
2907160
넳넲
Phoenix TRIO-UPS-2G/1AC/24DC/10-Uninterruptible Power Supply 2907161