Phoenix UNO2-PS/1AC/24DC/240W-power supply 1096432, primary switching power supply, UNO POWER, screw connection, DIN rail installation, input: 1 phase, output: 24V DC / 10 A, adjustable range 24V DC ... 28V DC

AC operation
Power System Configuration star network (TN,TT,IT (PE))
Rated input voltage range 100V AC ... 240V AC
Input Voltage Range 100V AC ... 240V AC -15 % ... +10%
Attenuation < 90V AC (1 %/V)
National Grid Typical Voltage 120V AC
230V AC
Supply Voltage AC
Impulse current Typical 10 A (at 25°C)
impulse current integral (I2t) < 0.2 A2s
frequency range (fN) 50Hz ... 60Hz ± 10%
grid buffer time Typical 16 ms (120V AC)
Typical 20 ms (230V AC)
power consumption 2.6 A (100V AC)
2.2 A (120V AC)
1.13 A (230V AC)
1.2 A (240V AC)
protection circuit transient surge protection; varistor, gas discharge tube
Suction time Typical 400 ms
Device Power Fuse 5 A built-in (device protection) fast fuse
recommend use 6 A ... 16 A (characteristics B, C, D, K or similar)
PE discharge current < 3.5 mA

efficiency Typical 92% (120V AC)
94% typical (230V AC)
Rated output voltage 24V DC
output voltage (USet) setting range 24V DC ... 28V DC (> 24V DC, stable capacity limit)
Rated output current (IN) 10 A
Short-circuit protection is
Anti-aircraft turn is
amplitude factor Typical 1.65 (120V AC)
Typical 1.63 (230V AC)
output power (PN) 240W
and connect Yes, for redundancy
Concatenation Yes, for higher output voltages
feedback voltage resistance ≤ 35V DC
output ≤ 35V DC
residual wave 50 mV typicalSS(rated value)
control deviation <1% (load change, static 10%... 90%)
<3% (load change, dynamic 10%... 90%)
< 0.1 % (input voltage variation is ± 10 %)
rise time < 1 s (UOut= 10%... 90%)
minimum no-load power consumption < 4W (120V AC)
maximum no-load power consumption < 4W (230V AC)
minimum rated load power consumption < 21W (120V AC)
1096432

Phoenix UNO2-PS/1AC/24DC/240W-Power 1096432

Product Center

PRODUCT CENTER