Phoenix PLC-RSC- 24DC/ 1IC/ACT-relay module 2967604,PLC-INTERFACE suitable for high inrush current, including PLC-BSC.../1 IC/ACT base terminal, using screw connection, with plug-in miniature relay, for installation On DIN rail NS 35/7.5, the inrush current is up to 130 A,1 normally open contact, input voltage 24V DC
Product Type
Relay Module
Product Series
PLC-INTERFACE
Application
Large impact current
Mode of operation
100% operating factor
mechanical life
3x 107Switch Times
Insulation Characteristics: Standards/Regulations
insulation
safety isolation, reinforced insulation
Overvoltage Category
III
pollution level
3
Data Management Status
Last data maintenance date
19.03.2025
rated conditions
0.43W
test voltage (coil/contact)
4 kV AC (50Hz,1 min, coil/contact)
Standards/Regulations
Rated insulation voltage
250V AC
Rated overvoltage
6 kV
coil side
Rated input voltage UN
24V DC
Input Voltage Range
20.2V DC ... 33.6V DC (20 °C)
rated voltage ("hot" plug electromagnetic relay)
24V DC
drives and functions
monostable
drive (polarity)
polarization
UN
18 mA
Typical Response Time
8 ms
Typical release time
10 ms
protection circuit
polarity protection; polarity protection diode
backup diode; freewheeling diode
Operating voltage display
yellow LED
switching
Contact Type
1 N/O contact
Switch Contact Type
Single contact
Contact Material
AgSnO
maximum switching voltage
250V AC/DC (When the voltage between the same terminals of two adjacent modules is greater than 250V(L1, L2, L3), a spacer PLC-ATP must be used. FBST 8-PLC... or... FBST 500... for equipotential bridging)
Minimum Switching Voltage
12V (100 mA)
limit continuous current
6 A
10 A (applicable if terminals 13, 14 and BB are shorted)
Maximum impact current
80 A (20 ms)
130 A (peak, capacitive load, 230V AC, 24 μF)
minimum switching current
100 mA (12 V)
Maximum power rating (resistive load)
144W (24V DC)
58W (available for 48V DC)
48W (available for 60V DC)
50W (available for 110V DC)
80W (available for 220V DC)
85W (250V DC)
1500 VA (available for 250V AC)
bridge power rating (resistive load)
240W (24V DC. This applies if terminals 13, 14 and BB are shorted)