Phoenix PLC-RSC- 48DC/21-21AU-Relay module 2967280,PLC-INTERFACE, including PLC-BSC.../21 base terminals, using screw connection, with plug-in miniature multi-layer gold-plated contact relay, for installation on DIN rail NS 35/7.5, 2 PDT, input voltage 48V DC

Product Type Relay Module
Product Series PLC-INTERFACE
Application General
Mode of operation 100% operating factor
mechanical life 3x 107Switch Times
insulation characteristics
insulation Foundation Isolation
Overvoltage Category III
pollution level 3
Data Management Status
Last data maintenance date 19.03.2025

rated conditions 0.96W
test voltage (coil/contact) 4 kV AC (50Hz,1 min, coil/contact)
test voltage (changeover contact/changeover contact) 2.5 kV AC (50Hz,1 minute, changeover contact/changeover contact)
Rated overvoltage 6 kV

coil side
Rated input voltage UN 48V DC
Input Voltage Range 40.3V DC ... 60V DC (20 °C)
rated voltage ("hot" plug electromagnetic relay) 24V DC
drives and functions monostable
drive (polarity) polarization
UN 20 mA
Typical Response Time 8 ms
Typical Release Time 10 ms
protection circuit polarity protection; polarity protection diode
backup diode; freewheeling diode
Operating voltage display yellow LED

switching
Contact Type 2 changeover contacts
Switch Contact Type Single contact
Contact Material AgNi, hard gold plating
maximum switching voltage 30V AC
36V DC
Minimum Switching Voltage 100 mV (10 mA)
limit continuous current 50 mA
Maximum impact current 50 mA
minimum switching current 1 mA (24 V)
Maximum power rating (resistive load) 1.2W (24V DC)
switching: when the gold plating layer is destroyed
Considerations If the gold plating is damaged, the following values are applicable.
maximum switching voltage 250V AC/DC
Minimum Switching Voltage 5V AC/DC
limit continuous current 6 A
Maximum impact current 15 A (300 ms)
2967060

Phoenix PLC-RSC- 48DC/21-21AU-Relay Module 2967280