Phoenix PLC-RSC-120UC/ 1AU/SEN-relay module 2966320,PLC-INTERFACE suitable for input functions, including PLC-BSC.../SEN base terminals, using screw connection, with plug-in miniature multi-layer gold-plated contact relay, for installation On DIN rail NS 35/7.5, 1 normally open contact, input voltage 120V AC/110V DC
Product Type
Relay Module
product series
PLC-INTERFACE
Application
input function
Mode of operation
100% operating factor
mechanical life
2x 107Switch Times
Data Management Status
Last data maintenance date
19.03.2025
rated conditions
0.42W
test voltage (coil/contact)
4 kV AC (50Hz,1 min, coil/contact)
insulation characteristics: coil/contact
Rated insulation voltage
250V
Rated impulse withstand voltage
6 kV
Overvoltage Level
III
pollution level
3
coil side
Rated input voltage UN
120V AC
110V DC
Input Voltage Range
93.6V AC/DC ... 168V AC/DC (20 °C)
rated voltage ("hot" plug electromagnetic relay)
60V DC
drives and functions
monostable
drive (polarity)
polarization
UN
3.5 mA
Typical Response Time
6 ms
Typical release time
15 ms
protection circuit
bridge rectifier
Operating voltage display
yellow LED
switching
Contact Type
1 N/O contact
Switch Contact Type
Single contact
Contact Material
AgSnO, hard gold plating
maximum switching voltage
30V AC
36V DC
Minimum Switching Voltage
100 mV (at 10 mA)
limit continuous current
50 mA
Maximum impact current
50 mA
minimum switching current
1 mA (24 V)
short-circuit current
200 A (condition short-circuit current)
Maximum power rating (resistive load)
1.2W (24V DC)
output fuse
4 A gL/gG NEOZED
switching: when the gold plating layer is destroyed
Considerations
If the gold plating is damaged, the following values are applicable.