Phoenix PLC-V8C/PT-24DC/EM-expansion module 2905137,PLC logic expansion module, with 16 I/O, pluggable connection to 8 PLC-INTERFACE modules to expand the basic module (up to 2 expansion modules can be connected to the basic module), in-line connection
| Product Type | Expansion Module |
| Product Series | PLC logic |
| Mode of operation | 100% operating factor |
| insulation characteristics: electrical clearance and creepage distance | |
| insulation | Foundation Isolation |
| Overvoltage Category | III |
| pollution level | 2 |
| electrical clearance and creepage distance | |
| Rated insulation voltage | 50V |
| Rated overvoltage | 0.8 kV |
| Power | |
| supply voltage | 24V DC |
| Supply Voltage Range | 19.2V DC ... 26.4V DC |
| Maximum input current UN | 65 mA |
| protection circuit | polarity protection |
| Surge Protection | |
| Digital Input | |
| Input Quantity | 8 (2 can be configured as analog) |
| Input Description | EN 61131-2, Class 3 |
| input voltage | 24V DC |
| signal level "0" signal | < 5V |
| signal level "1" signal | > 11V |
| input current, "0" signal | < 1 mA |
| input current, "1" signal | Typical 2.5 mA |
| Status Display | LED (yellow) |
| Analog Input | |
| Input Quantity | 2 (IN6 and IN7 can be configured as analog) |
| Input Voltage Range | 0V ... 10V |
| input resistance | > 3.5 kΩ |
| contact PLC-INTERFACE | |
| Input Quantity | ≤ 8 |
| Input Description | Technical data depends on the PLC-INTERFACE terminal used |
| input voltage | 19V DC |
| Typical current consumption | 4 mA |
| input resistance | < 100 mΩ |
| outputs | ≤ 8 |
| Rated output voltage | 24V DC |
| Rated current | 9 mA |