Phoenix PSR-MC30-2NO-1DO-24DC-SP-safety relay 2700499, safety relay, used for emergency stop and safety door, safety level up to SIL 3, Cat. 4, PL e, single-channel or dual-channel operation, automatic or manual, controlled start, Cross circuit detection, 2 enable current paths, US = 24V DC, "hot" plug-in terminal

Product Type safety relay
Product Series PSRmini
Application Emergency stop button
safety door
electromagnetic switch
control dual channel
mechanical life about 107Switch Times
Relay Model Electromechanical relay with mechanical interlocking contacts according to IEC/EN 61810-3
insulation characteristics
Overvoltage Level III
pollution level 2
Typical Response Time < 175 ms (auto start)
< 175 ms (manual, monitoring start)
typical startup time (Us) < 250 ms (when controlled via A1)
Typical Release Time < 20 ms (as required, via A1)
< 20 ms (via sensor loop as required)
restart time < 1 s (start-up time, after power supply voltage is applied)
Recovery Time < 500 ms (meets the requirements of safety functions)
Start Pulse Length 500 ms (manual reset)

rated conditions 5.5W (US= 26.4 V, IL² = 72 A²,PTotal max=1.9W +3.6 W)
Rated operating mode 100% Eligible
Rated insulation voltage 250V AC
rated overvoltage/insulation input circuit and normally open safety contact output (13/14) and normally open safety contact output (23/24)
4 kV foundation safety isolation between all current paths and enclosure
power supply
Name A1/A2
Rated control circuit supply voltage US 20.4V DC ... 26.4V DC
Rated control circuit supply voltage US 24V DC -15 % / +10%
Rated control supply current IS typical value 65 mA (US)
US Typical 1.56W
Impulse current typical 4 A (& Delta;t = 200 & micro;s Us)
filter time 1 ms (at A1, at the voltage dip Us)
protection circuit series protection to prevent polarity reversal; suppression diode

digital quantity: sensor circuit (S11, S12, S21, S22)
Input Description safety-related sensor inputs
Input Quantity 4
input voltage range, "0" signal < 5V (S12)
S22 interprets the low resistance output of the PLC as a continuous high signal.
input voltage range, "1" signal 20.4V ... 26.4V
Input current range "0" signal < 2 mA (S12)
0 mA ... 2 mA (S22)
Impulse current < 20 mA (S12 input, the voltage is usually US)
< 5 mA (typically USS22/24 V)
> -15 mA (typically USS22/0 V)
filter time max. 1.5 ms (at S12, S22; test pulse width)
7.5 ms minimum (at S12, S22; test pulse rate)
test pulse rate = 5 x test pulse width
parallel
Allowable Total Conductor Resistance 150 Ω
2700499