Phoenix PSR-MC37-3NO-1NC-24DC-SC-safety relay 2702411, safety relay for emergency stop, safety door and elevator, safety level up to SIL 3, Cat. 4 and PL e, single-channel or dual-channel operation, automatic or manual start, cross circuit detection, 3-way normally open safety contact output, US = 24V DC, pluggable screw terminal

Product Type safety relay
product series PSRmini
Application Emergency stop button
safety door
electromagnetic switch
answering machine
control Single and Dual Channel
Relay Model Electromechanical relay with mechanical interlocking contacts according to IEC/EN 61810-3
insulation characteristics
Overvoltage Level II
pollution level 2
Typical Response Time < 100 ms (auto start)
Typical startup time (Us) < 100 ms (when controlled via A1)
Typical release time < 20 ms (when controlled via A1 or S12 and S22)
restart time < 1 s (start-up time)
Recovery Time < 500 ms

rated conditions 17.03W (UB= 30V ,US= 24V ,IS= 70 mA, IL2= 72 A2,RContact= 0.2) H.
Rated operating mode 100% Eligible
Rated insulation voltage 250V AC
rated overvoltage/insulation 4 kV base safety isolation between all current paths
4 kV basic insulation between all current paths and enclosure
power supply
Name A1/A2
Rated control circuit supply voltage US 19.2V DC ... 30V DC
Rated control circuit supply voltage US 24V DC -20 % / +25%
Rated control supply current IS Typical 70 mA
US Typical 1.68W
Impulse current 2 A (&Delta;t = 300 &micro;s Us)
protection circuit series protection to prevent polarity reversal; suppression diode

digital quantity: sensor circuit (S12,S22)
Input Description safety-related sensor inputs
Input Quantity 2
input voltage range, "0" signal < 5V (S12)
0V DC ... 5V DC (S22)
Input current range "0" signal < 2 mA (S12)
0 mA ... 2 mA (S22)
Impulse current < 5 mA (the voltage is usually U at S12S,&Delta;t = 500 &micro;s)
< 5 mA (typically USS22/24 V,&Delta;t = 500 &micro;s)
> -5 mA (typically USS22/0 V,&Delta;t = 500 &micro;s)
filter time max. 3 ms (at S12 and S22; test pulse width; blanking pulse/dark test)
> 1 s (at S12 and S22; test pulse rate; blanking pulse/dark test)
test pulse width ≤ 1 ms: test pulse rate = 5 x test pulse width
max. 1 ms (at S12 and S22: test pulse width; switching pulse/optical gap test)
> 100 ms (at S12 and S22; test pulse rate; switching pulse/optical gap test)
is disabled unless the test pulse is of safety relevance.
Allowable Total Conductor Resistance 150 Ω
protection circuit suppression diode
power consumption < 4 mA (S12 input, the voltage is usually US)
< 4 mA (typically USS22/24 V)
> -15 mA (typically USS22/0 V)
2702411

Phoenix PSR-MC37-3NO-1NC-24DC-SC-Safety Relays 2702411

Product Center

PRODUCT CENTER