Phoenix PSR-M-EF7-SAI4-PI-expansion module 1104986, safety expansion module, with 4 safety analog inputs, 0V ... 10V;0 mA or 4 mA ... 20 mA;TBUS interface, safety level up to Cat. 4/PL e, SIL 3, plug-in connection with plug-in connection, with TBUS connector attached

Product Type safety equipment
Application Analog Input
control Single and Dual Channel
insulation characteristics
protection level III
insulation characteristics
Overvoltage Level II
pollution level 2
response time See User Manual
restart time min. 5 s (start-up time)
max. 10 s (start-up time)

rated conditions 2.76W (with maximum allowable load)
Rated operating mode 100% Eligible
Interface DIN rail TBUS for connecting the host module, within the scope of delivery
rated overvoltage/insulation 4 kV basic safety isolation between all current paths and enclosure
galvanic isolation with 0.5 kV functional isolation between logic and analog inputs and between analog inputs
Power
Name A1/A2
Rated control circuit supply voltage US 19.2V DC ... 28.8V DC
Rated control circuit supply voltage US 24V DC-20%/+ 20% (external fuse, typical 6 A)
Rated control supply current IS Typical 82 mA (without sensor power)
Typical 212 mA (with sensor power)
US Typical 1.96W (without sensor power)
Typical 5.08W (with sensor power supply)
Impulse current max. 14 A (& Delta;t = 1 ms Us)
filter time typical 5 ms (Usvoltage dips)
protection circuit series protection to prevent polarity reversal

Overview
protection circuit current input; suppression diode
simulation
Enter Name IN S1, IN S2, IN S3, IN S4
Input Description Safety-oriented analog input, configurable as current or voltage input, potential isolation
Input Quantity 4
connection system 2-wire, 3-wire or 4-wire (2-wire sensor signal 2-wire sensor power supply)
Notes on connection technology Shielding
scanning frequency 2.5/5/10/16.6/20/50/60/100/200/400/800/1000/2000/4000Hz
current input signal 0 mA ... 25 mA (measuring range)
0 mA ... 20 mA (configurable measuring range with diagnostic range of 20.1 mA ... 23 mA)
4 mA ... 20 mA (configurable measuring range with diagnostic range of 20.1 mA ... 23 mA (upper limit), 2.5 mA ... 3.8 mA (lower limit))
voltage input signal 0V ... 12V (measuring range)
0V ... 10V (configurable measuring range with diagnostic range of 10.05V ... 11.5V (upper limit), 0.1V (lower limit))
maximum allowable current maximum 35 mA (as current input)
allowable voltage 24V max (as current input)
max. 14V (as voltage input)
input current 290 Ω ± 25% (including internal protection circuit)
input voltage 185 kΩ ±25%
A/D converter resolution 16 bits
resolution (current) 381 nA
resolution (voltage) 152 µV
accuracy . ± 2% (as current input, relative to the final value of the measurement range)
max. ± 2.5 % (as current input)
typical. ± 1% (as voltage input, relative to the final value of the measuring range)
max. ± 1.5 % (as voltage input)
temperature coefficient Typical. ± 0.07 %/K
max. ± 0.07 %/K
cut-off frequency (3dB) 160Hz (RC low-flux, 1st order, as current input