Phoenix PSR-PLC21-2CO-24DC-SC-coupling relay 1480226, safety coupling relay, with mechanical interlocking contact, electrical isolation, 2 changeover contacts, single channel, fixed screw terminal block, width: 14mm

Product Type coupling relay
product series PLC-INTERFACE
Application forced guide contact
mechanical life about 107Switch Times
Relay Model electromechanical relay according to IEC/EN 61810
insulation characteristics: electrical clearance and creepage distance between power supply circuits
Overvoltage Category III
pollution level 2
Typical startup time (Us) < 70 ms (when controlled via A1)
Typical release time < 50 ms (as required, via A1)
Recovery Time 500 ms (in accordance with the requirements of safety functions)

rated conditions 4.825W (UB= 30 V,US= 24 V, IS= 30 mA, IL² = 37 A,Rcontact= 0.1 Ω)
Rated operating mode 100% Eligible
Electrical clearance and creepage distance between power supply circuits
Rated insulation voltage 250V AC
rated overvoltage/insulation 4 kV basic safety isolation between all current paths and enclosure
safety isolation with 6 kV enhanced isolation between 250V load current path and 24V logic path
Power
Name A1/A2
Rated control circuit supply voltage US 21.6V DC ... 28.8V DC
Rated control circuit supply voltage US 24V DC -10 % / +20%
Rated control supply current IS 30 mA
Impulse current Typical 100 mA (& Delta;t = 10 ms Us)
delay time 1 ms (test pulse width, high test pulse and low test pulse)
1 s (test pulse frequency, high test pulse and low test pulse)
UD 650 mW (to US)
protection circuit Series protection against polarity reversal; Suppressor diode, 38.6V/600W
Status Display 1 x Green LED(PWR)

relay: relay output (11/12/14, 21/22/24)
Output Description safety related
outputs 2
Contact Type 2 changeover contacts
Contact Material AgNi
on-off capacity 150 mW minimum (normally open contact/normally closed contact)
Impulse current max. 6 A (N/O contact)
max. 4 A (normally closed contact)
switching capacity according to IEC 60947-5-1 6 A (AC1, 230 V)
3 A (AC15, 230 V)
6 A (DC1,24V,N/O contact)
4 A (DC1,24V,N/C contact)
3 A (DC13,24V,N/O contact)
limit continuous current 6 A (normally open contact, high demand)
4 A (normally open contact, low requirement)
4 A (N/C contact, high on request)
2.4 A (N/C contact, low requirement)
the square of the total current value 37 A2(N/O contact, high requirements, observe attenuation curve)
16 A2(N/C contact, high requirements, observe the attenuation curve)
1480226

Phoenix PSR-PLC21-2CO-24DC-SC-Coupling Relay 1480226