Phoenix MCR-S-1-5-UI-DCI-NC-current transmitter 2814715,MCR current transmitter, programmable and configurable, can measure DC, AC and distortion current, input current 0...0.2 to 0...11 A, unconfigured
Product Type
Current transmitter
insulation characteristics
Overvoltage Category
III
pollution level
2
total error
≤ 1.5 % (temperature range)
rated conditions
2.2W
Measurement Level
III
test voltage, output/power supply
500V AC (50 Hz, 60 s)
test voltage, input/output
4 kV AC (50 Hz, 60 s)
test voltage, input/power supply
4 kV AC (50 Hz, 60 s)
protection circuit
surge protection; 33V suppressor diode
step response (10-90%)
330 ms (AC)
40 ms (DC)
temperature coefficient, typical
< 0.025 %/K
Maximum transmission error
< 0.5 % (at rated state, within rated range)
Rated insulation voltage
300V AC (ground)
Power
Supply Voltage Range
20V DC ... 30V DC
Maximum current consumption
< 40 mA (no load)
measurement
Input Number
3
configurable/programmable
Yes, not configured
Input current range
0 A AC/DC ... 11 A AC/DC (Allowable continuous overload: 120%)