Phoenix TTC-6-2X1-M-24DC-PT-I-surge protector 2906729, surge protection, built-in status indicator and breaking switch, used for two signal cables with common reference potential, such as digital IN/OUT. Can be used in safety-related circuits up to SIL 3.

Product Type measurement and control technology
Product Series TERMITRAB complete
IEC Category C1
C2
C3
D1
type rail mounting module, monolithic
insulation characteristics
Overvoltage Category III
pollution level 2

Rated voltage UN 24V DC

Connection Mode in-line connection
Flexible Wire Cross Section 0.2 mm² ... 2.5 mm²
Rigid conductor cross section 0.2 mm² ... 4 mm²
Attachable Guide Cross Section AWG 24 ... 12

Dimensional drawing
width 6.2mm 0.1mm
height 105.8mm
depth 83.5mm (7.5mm with DIN rail)

color gray (RAL 7042)
flame retardant rating to UL 94 V-0
insulation material PBT
Shell Material PBT

Mechanical parameters
Open Side Panel No

movement direction Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous voltage Uc 30V DC
21V AC
Rated current 600 mA (40°C)
UC, the effective working current IC ≤ 5 µA
Residual Flow IPE ≤ 10 µA
Rated discharge current In(8/20)& micro;s (core-ground) 5 kA
pulse discharge current Iimp(350) & micro;s (core-ground) 0.5 kA
Total discharge current ITotal(8/20) µs 10 kA
voltage protection level Up(line-ground) ≤ 140V (C1 - 1 kV / 500 A)
≤ 130V (C2 - 10 kV / 5 kA)
≤ 45V (C3 - 25 A)
≤ 50V (C3 - 100 A)
voltage protection level Upstatic (core-ground) ≤ 55V (C1 - 1 kV / 500 A)
≤ 80V (C2 - 10 kV / 5 kA)
response time tA (core-ground) ≤ 1 ns
input attenuation AE, asymmetric. Typical 0.3 dB (≤ 270 kHz/150 Ω)
cutoff frequency fg(3 dB), asymmetric. (PE) in the 150 Ω system Typical 960 kHz
2906776

Phoenix TTC-6-2X1-M-24DC-PT-I-Surge Protector 2906729

Product Center

PRODUCT CENTER