Phoenix TTC-6-3-HF-F-12DC-PT-surge protector 1109712, surge protection, used for three signal lines with a common reference potential. Suitable for high-frequency applications and communication interfaces without supply voltage (maximum rate 90 Mbps).
| Product Type | Information Technology |
| Product Series | TERMITRAB complete |
| IEC Category | C1 |
| C2 | |
| C3 | |
| D1 | |
| type | rail mounting module, monolithic |
| insulation characteristics | |
| Overvoltage Category | III |
| pollution level | 2 |
| Rated voltage UN | 12V DC |
| Connection Mode | in-line connection |
| Flexible Wire Cross Section | 0.2 mm² ... 2.5 mm² |
| Rigid conductor cross section | 0.2 mm² ... 4 mm² |
| Attachable Guide Cross Section AWG | 24 ... 12 |
| Dimensional drawing | |
| width | 6.2mm +0.1mm |
| height | 105.8mm |
| depth | 69.5mm (7.5mm with DIN rail) |
| color | gray (RAL 7042) |
| flame retardant rating, according to UL 94 | V-0 |
| insulation material | PBT |
| Shell Material | PBT |
| Mechanical parameters | |
| Open Side Panel | No |
| movement direction | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Maximum continuous voltage Uc | 15V DC |
| Rated current | 600 mA (40°C) |
| UC, the effective working current IC | ≤ 100 µA |
| Residual Flow IPE | ≤ 1 µA |
| Nominal discharge current In(8/20) & micro;s (core-core) | 5 kA |
| Rated discharge current In(8/20)& micro;s (core-ground) | 5 kA |
| pulse discharge current Iimp(350) & micro;s (core-ground) | 0.5 kA |
| Total discharge current ITotal(8/20) µs | 10 kA |
| voltage protection level Up(core-core) | ≤ 45V (C1 - 1 kV / 500 A) |
| ≤ 85V (C2 - 10 kV / 5 kA) | |
| ≤ 30V (C3 - 100 A) | |
| voltage protection level Up(line-ground) | ≤ 800V (C1 - 1 kV / 500 A) |
| ≤ 800V (C2 - 10 kV / 5 kA) | |
| ≤ 800V (C3 - 100 A) | |
| response time tA(core-core) | ≤ 1 ns |
| response time tA (core-ground) | ≤ 100 ns |
| input attenuation AE, symmetric. | Typical 0.3 dB (≤ 12 MHz / 150 Ω) |
| input attenuation AE, asymmetric. | Typical 0.3 dB (≤ 20 MHz / 150 Ω) |
| cut-off frequency fg(3 dB),150 Ω symmetric system | 60 MHz typical |
| cutoff frequency fg(3 dB), asymmetric. (PE) in the 150 Ω system | 60 MHz typical |
| capacitance (core-core) | Typical 32 pF |
| capacitance (core-ground) | Typical 32 pF |
| the resistance of each path | 1.65 Ω ± 20% |
| Surge protection fault alarm | None |
| 630 mA (FF) | |
| Impact tolerance (line-line) | C1 - 1 kV / 500 A |
| C2 - 10 kV / 5 kA | |
| C3 - 100 A |