Phoenix TTC-6P-1X2-24DC-UT-I-surge protector 2906809, surge protection, including protection plug and base element, built-in status indicator, used for 2-wire floating signal loop, such as 0(4) mA ... 20 mA current cycle, HART compatible. Can be used in safety-related circuits up to SIL 3.
Product Type
measurement and control technology
Product Series
TERMITRAB complete
IEC Category
C1
C2
C3
D1
type
DIN rail module, split, detachable
line pairs per module
1
insulation characteristics
Overvoltage Category
III
pollution level
2
Rated voltage UN
24V DC
Connection Mode
screw connection
thread
M3
Tightening torque
0.5 Nm ... 0.6 Nm
Flexible Wire Cross Section
0.2 mm² ... 2.5 mm²
Rigid conductor cross section
0.2 mm² ... 4 mm²
Connectable Guide Cross Section AWG
24 ... 12
Dimensional drawing
width
6.2mm 0.1mm
height
105.8mm
depth
100 mm (7.5mm with DIN rail)
color (basic element)
gray (RAL 7042)
color (pin connector)
light gray (RAL 7035)
flame retardant rating, according to UL 94
V-0
insulation material
PBT
Shell Material
PBT
Mechanical parameters
Open Side Panel
No
movement direction
Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous voltage Uc
30V DC
21V AC
Rated current
600 mA (56°C)
UC, the effective working current IC
≤ 5 µA
Residual Flow IPE
≤ 1 µA
Nominal discharge current In(8/20) & micro;s (core-core)
5 kA
Rated discharge current In(8/20)& micro;s (core-ground)
5 kA
pulse discharge current Iimp(350) & micro;s (core-core)
0.5 kA
pulse discharge current Iimp(350) & micro;s (core-ground)