Phoenix TTC-6P-1X2-M-24DC-PT-I-surge protector 2906750, surge protection, including protection plug and base element, built-in status indicator and breaking switch, used for 2-wire floating ground signal circuit, such as 0(4) ... 20 mA Current cycle, suitable for Ex e certification in Zone 2, HART compatible. Can be used in safety-related circuits up to SIL 3.
Product Type
measurement and control technology
Product Series
TERMITRAB complete
IEC Category
C1
C2
C3
D1
type
DIN rail module, split, detachable
line pairs per module
1
insulation characteristics
Overvoltage Category
III
pollution level
2
Rated voltage UN
24V DC
Connection Mode
in-line connection
Flexible Wire Cross Section
0.2 mm² ... 2.5 mm²
Rigid conductor cross section
0.2 mm² ... 4 mm²
Connectable Guide Cross Section AWG
24 ... 12
Maximum input current
600 mA (T4 / ≤ 30°C)
500 mA (T4 / > 30°C ... ≤ 50°C)
400 mA (T4 / > 50°C ... ≤ 70°C)
Maximum input voltage
30V DC
elevation
≤ 2000 m (amsl)
ambient temperature (operation)
-40°C ... 70°C (T4)
Dimensional drawing
width
6.2mm 0.1mm
height
105.8mm
depth
100 mm (7.5mm with DIN rail)
color (basic element)
gray (RAL 7042)
color (pin connector)
light gray (RAL 7035)
flame retardant rating, according to UL 94
V-0
insulation material
PBT
Shell Material
PBT
Mechanical parameters
Open Side Panel
No
Direction of action
Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground
Maximum continuous voltage Uc
30V DC
21V AC
Rated current
600 mA (56°C)
UC, the effective working current IC
≤ 5 µA
Residual Flow IPE
≤ 1 µA
Nominal discharge current In(8/20) & micro;s (core-core)
5 kA
Rated discharge current In(8/20)& micro;s (core-ground)
5 kA
pulse discharge current Iimp(350) & micro;s (core-core)
0.5 kA
pulse discharge current Iimp(350) & micro;s (core-ground)