Phoenix TTC-6P-T3-24DC-PT-I-3 surge protection equipment 1027586, type 3 surge protection, including protective connectors and base elements, built-in status indicator for 24V DC power supply
Overview
Considerations
CBM:
2905743 CBM E4 24DC/0.5-10A NO-R
2905744 CBM E8 24DC/0.5-10A NO-R
CBMC:
2906032 CBMC E4 24DC/1-10A NO
2908716 CBMC E4 24DC/1-10A NO-C
2910411 CBMC E4 24DC/1-10A IOL
PTCB:
2908262 PTCB E1 24DC/1-8A NO
CB E1:
2800907 CB E1 24DC/10A NO P
2800914 CB E1 24DC/10A S-R P
2800928 CB E1 24DC/10A S-C P
2905805 CB E1 24DC/10A SI-R P
2905812 CB E1 24DC/10A SI-C P
Product Type
Equipment Protection
Product Series
TERMITRAB complete
IEC power supply system
DC
type
DIN rail module, split, detachable
Bits
2
Surge protection fault alarm
with visual status indication window
insulation characteristics
Overvoltage Category
III
pollution level
2
IEC Category
III
T3
EN Type
T3
Ports
One
Connection Mode
in-line connection
Flexible Wire Cross Section
0.2 mm² ... 2.5 mm²
Rigid conductor cross section
0.2 mm² ... 4 mm²
Attachable Guide Cross Section AWG
24 ... 12
Dimensional drawing
width
6.2mm +0.1mm
height
105.8mm
depth
100 mm (7.5mm with DIN rail)
color (basic element)
gray (RAL 7042)
color (pin connector)
light gray (RAL 7035)
flame retardant rating, according to UL 94
V-0
material
600
insulation material
PBT
Shell Material
PBT
power supply
movement direction
1L-N & N-PE
Rated voltage UN
24V DC
Maximum continuous voltage Uc
30V DC
Rated load current IL
6 A (30 °C)
Residual Flow IPE
≤ 5 µA
Nominal discharge current In(8/20)µs
1 kA
Combined surge UOC
2 kV (2 Ω)
2 kV (2 Ω)
voltage protection level Up(DC+) - (DC-)
≤ 0.09 kV (Uoc= 2 kV)
≤ 0.2 kV (Uoc= 6 kV)
voltage protection level Up(DC+/DC-) - PE
≤ 0.7 kV
Rated short-circuit current ISCCR
60 A DC (no additional backup protection fuse required)
220 A DC
maximum spare fuse with branch wiring
6 A (gG)
10 A (see instructions: CBM, CBMC, PTCB, CB E1)
environmental conditions
protection level
IP20
Ambient temperature (operation)
-40°C ... 80°C
ambient temperature (storage/transport)
-40°C ... 80°C
elevation
≤ 6000 m (amsl)
Allowable humidity (operating)
5%... 95%
Impact Force (Operation)
30g (half sine/11 ms/ 3x ± X,± Y, ± Z)
vibration (operation)
5g (10 ... 150Hz/20 times/axis/X, Y, Z)
2906815
넳넲