Phoenix Class PLT-SEC-T3-230-FM-UT-3 Surge Protective Device 2907919, Type 2/3 Surge Protective Device, consisting of a protective connector and a base element with a screw connection. Single-phase power network for built-in status indicator and remote signaling. Rated voltage: 230V AC/DC
| Product Type | Equipment Protection |
| product series | SEC Family |
| IEC power supply system | TT |
| TN-S | |
| type | DIN rail module, split, detachable |
| Bits | 2 |
| Surge protection fault alarm | visual status indication window and remote alarm contact |
| insulation characteristics | |
| Overvoltage Category | III |
| pollution level | 2 |
| IEC Category | II / III |
| T2 / T3 | |
| EN Type | T2 / T3 |
| Ports | One |
| indicator/remote signaling | |
| Connection Name | Remote alarm contact |
| switching function | changeover contact |
| Nominal operating voltage | 250V AC |
| 125V DC (200 mA DC) | |
| working current | 0.5 A AC |
| 0.5 A DC (75V DC) | |
| Connection Mode | screw connection |
| thread | M3 |
| Tightening torque | 0.5 Nm |
| Flexible Wire Cross Section | 0.2 mm² ... 2.5 mm² |
| Rigid conductor cross section | 0.2 mm² ... 4 mm² |
| Connectable Guide Cross Section AWG | 24 ... 12 |
| Dimensional drawing | |
| width | 17.7mm |
| height | 93.4mm |
| depth | 74.5mm (7.5mm with DIN rail) |
| Horizontal stitch pitch | 1 Partition |
| color (pin connector) | light gray (RAL 7035) |
| color (basic element) | gray (RAL 7042) |
| flame retardant rating, according to UL 94 | V-0 |
| material | 600 |
| insulation material | PA 6.6-FR 20 % GF |
| PA 6.6-FR | |
| Shell Material | PA 6.6-FR 20 % GF |
| PA 6.6-FR |
| protection channel | L-N |
| L-PE | |
| N-PE | |
| Direction of action | 1L-N & N-PE |
| Rated voltage UN | 240V AC (TN-S) |
| 240V AC (TT) | |
| Rated frequency fN | 50Hz (60 Hz) |
| Maximum continuous voltage Uc | 264V AC |
| Rated load current IL | 26 A (at 30°C) |
| Residual Flow IPE | ≤ 5 µA |
| Standby power consumption PC | ≤ 26.4 mVA (UREF) |
| ≤ 26.4 mVA (UC) | |
| Reference test voltage UREF | 264V AC |
| Nominal discharge current In(8/20)µs | 5 kA |
| Maximum discharge current Imax(8/20) µs | 10 kA |
| Combined surge UOC | 6 kV |
| voltage protection level Up(L-N) | ≤ 1.25 kV (UOC) |
| ≤ 1.4 kV (In) | |
| voltage protection level Up(L-PE) | ≤ 1.4 kV |
| voltage protection level Up(N-PE) | ≤ 1.4 kV |
| UT(L-N) | 400V AC (5 seconds/withstand mode) |
| 457V AC (120 min/safe failure mode) | |
| UT(L-PE) | 457V AC (5 seconds/withstand mode) |
| 457V AC (120 min/tolerance mode) | |
| 1464V AC (200 ms/SAFE mode) |