Phoenix PLT-SEC-T3-3S-230-P-3 Class Surge Protector-Plug and Plug 2905236, Spare Plug, Used for Type 3 Device Protection PLUGTRAB SEC T3 3S Product Series. Nominal voltage 230V.
| Product Type | Spare Plug |
| Product Series | SEC Family |
| IEC power supply system | TN-S |
| TT | |
| type | needle type |
| Bits | 4 |
| Surge protection fault alarm | with visual status indication window |
| insulation characteristics | |
| Overvoltage Category | III |
| pollution level | 2 |
| IEC Category | III |
| T3 | |
| EN Type | T3 |
| Connection Mode | pluggable |
| Dimensional drawing | |
| width | 35.2mm |
| height | 44.8mm |
| depth | 60.9mm |
| Horizontal stitch pitch | Division 2 |
| color | light gray (RAL 7035) |
| flame retardant rating, according to UL 94 | V-0 |
| material | 600 |
| insulation material | PA 6.6-FR 20% GF |
| PA 6.6-FR | |
| Material Group | I |
| Shell Material | PA 6.6-FR 20 % GF |
| PA 6.6-FR |
| protection channel | L-N |
| L-PE | |
| N-PE | |
| movement direction | 3L-N & N-PE |
| Rated voltage UN | 230/400V AC (TN-S) |
| 230/400V AC (TT-only with RCD) | |
| Rated frequency fN | 50Hz (60 Hz) |
| Maximum continuous voltage Uc | 264V AC |
| Residual Flow IPE | ≤ 5 µA |
| Standby power consumption PC | ≤ 2 VA (UREF) |
| ≤ 2.2 VA (UC) | |
| Reference test voltage UREF | 255V AC |
| Nominal discharge current In(8/20)µs | 3 kA |
| Combined surge UOC | 6 kV |
| voltage protection level Up(L-N) | ≤ 1.4 kV |
| voltage protection level Up(L-PE) | ≤ 1.5 kV |
| voltage protection level Up(N-PE) | ≤ 1.5 kV |
| UT(L-N) | 440V AC (5 seconds/withstand mode) |
| 440V AC (120 min/tolerance mode) | |
| UT(L-PE) | 440V AC (5 seconds/withstand mode) |
| 440V AC (120 min/tolerance mode) | |
| 1455V AC (200 ms/safety failure mode) | |
| UT(N-PE) | 1200V AC (200 ms/SAFE mode) |
| response time tA(L-N) | ≤ 25 ns |
| response time tA(L-PEN) | ≤ 100 ns |
| response time tA(N-PE) | ≤ 100 ns |
| Rated short-circuit current ISCCR | 1.5 kA AC |
| environmental conditions | |
| protection level | IP20 |
| ambient temperature (operation) | -40°C ... 70°C |
| ambient temperature (storage/transport) | -40°C ... 70°C |
| elevation | ≤ 2000 m (amsl) |
| Allowable humidity (operating) | 5%... 95% |
| Impact Force (Operation) | 30g (half sine/11 ms/ 3x ± X,± Y, ± Z) |
| vibration (operation) | 5g (10 ... 150Hz/20 times/axis/X, Y, Z) |