Phoenix CAPAROC PD 0V-potential distribution terminal 1110987, potential distributor with plug-in connection, used to directly connect the 0V return line in the CAPAROC system. Suitable for DIN rail mounting via CAPAROC bus bars.
Product Type
Equipment circuit breaker
Product Series
CAPAROC
type
Plug-in Modules
slots
1
insulation characteristics
protection level
III
pollution level
2
Overview
working voltage
0V DC ... 30V DC
Rated voltage
12V DC
24V DC
Nominal operating current IN
4x 10 A DC (each output)
2x 20 A DC (each output)
40 A DC (total)
Rated overvoltage
0.5 kV
efficiency
> 99%
power consumption
< 0.4W (nominal operation at 24V and 4 x 10 A)
MTBF (IEC 61709, SN 29500)
269532625 h (25°C, 21% load)
269532334.5 h (40°C at 34.25% load)
269530881.5 h (at 60°C, 100% load)
voltage drop
9.7 mV (10 A)
Load Circuit
Connection Mode
in-line connection
stripping length
10mm
Flexible Wire Cross Section
0.2 mm² ... 4 mm²
Rigid conductor cross section
0.2 mm² ... 4 mm²
Attachable Guide Cross Section AWG
24 ... 12
Flexible conductor cross-section, with sleeve, with plastic insulation sleeve
0.25 mm² ... 4 mm²
flexible conductor cross-section with cold press head without insulation sleeve
0.25 mm² ... 4 mm²
Dimensional drawing
width
6.2mm
height
132.4mm
depth
109.9mm (7.5mm with DIN rail)
color
light gray (RAL 7035)
Identification Materials
PA 6
PA 6
PA 6
flame retardant rating, according to UL 94
V-0
environmental conditions
protection level
IP20
Ambient temperature (operation)
-30°C ... 65°C (must take into account the temperature range of the power module)
ambient temperature (storage/transport)
-40°C ... 70°C
elevation
≤ 4000 m (amsl)
Humidity determination
96 h,95 % RH,40 °C
Impact Force (Operation)
30g (11 ms period, half-sine shock pulse according to IEC 60068-2-27)
25g (6 ms duration, half-sine shock pulse according to IEC 60068-2-27, continuous shock)
vibration (operation)
5g (10Hz ... 150Hz / 10 times/axis/X, Y, Z)
1110984
넳넲
Phoenix CAPAROC PD 0V-potential distribution terminal 1110987