Phoenix FLT-MB-T1-264/25-3 0-UT-R - 1 2 3 combined surge protector 1461302, compact, non-"hot" plug-in and leakage-free lightning current/surge protector based on wear-free carbon discharge gap technology, used for 3-phase power supply network (4-wire system: L1, L2, L3, PEN) with common N (neutral wire) and PE (protective wire), suitable for use in unmeasured areas, discharge capacity up to 100 kA, lightning protection class I and II, with remote signaling function.
Product Type
combination type
IEC Category
I II III
T1 T2 T3
EN Type
T1 T2 T3
IEC power supply system
TN-C
type
rail mounting module, monolithic
Surge protection fault alarm
visual status indication window and remote alarm contact
insulation characteristics
Overvoltage Category
IV (main circuit)
II (auxiliary circuit)
pollution level
2
Rated frequency fN
50Hz (60 Hz)
indicator/remote signaling
Connection Name
Remote alarm contact
switching function
changeover contact
Nominal operating voltage
12V AC ... 250V AC
125V DC (200 mA DC)
Operating current
10 mA AC ... 0.5 A AC
0.5 A DC (30V DC)
Connection Mode
screw connection
thread
M5
Tightening torque
3 Nm (2,5 mm² ... 16 mm²)
4.5 Nm (25 mm² ... 35 mm²)
stripping length
18mm
Flexible Wire Cross Section
2.5 mm² ... 25 mm²
Rigid conductor cross section
2.5 mm² ... 35 mm²
Attachable Guide Cross Section AWG
13 ... 2
Connection Mode
fork cable end
Flexible Wire Cross Section
2.5 mm² ... 25 mm²
Remote alarm contact
Connection Mode
COMBICON in-line/screw connection
thread
M2
Tightening torque
0.5 Nm ... 0.6 Nm
stripping length
7mm
Flexible Wire Cross Section
0.2 mm² ... 2.5 mm²
Rigid conductor cross section
0.2 mm² ... 2.5 mm²
Attachable Guide Cross Section AWG
24 ... 12
Dimensional drawing
width
72mm
height
99.7mm
depth
76.6mm (7.5mm with DIN rail)
Horizontal stitch pitch
4 Zoning
color
light gray (RAL 7035)
flame retardant rating to UL 94
V-0
material
600
insulation material
PBT
Material Group
I
Shell Material
PBT
Mechanical parameters
Open Side Panel
No
protection channel
L-PEN
Rated voltage UN
240/415V AC (TN-C)
Rated frequency fN
50Hz (60 Hz)
Maximum continuous operating voltage UC
264V AC
Rated load current IL
80 A (< 55 °C)
Residual Flow IPE
≤ 0.01 mA
Nominal discharge current In(8/20)µs
25 kA
Combined surge UOC
6 kV
impulse discharge current (10/350)& micro;s, charging
12.5
impulse discharge current (10/350)& micro;s, specific energy