Phoenix PT-IQ-3-HF-12DC-PT-surge protector 2801288, surge protection device, composed of protective plugs and basic components, the module has built-in multi-level status indicators, which can be used for three signal lines with a common reference potential. Suitable for high-frequency applications and telecommunications interfaces without supply voltage (maximum rate 90 Mbps). Can be used in safety-related circuits up to SIL 3.
| Product Type | Information Technology |
| Product Series | PLUGTRAB IQ |
| IEC Category | C1 |
| C2 | |
| C3 | |
| D1 | |
| type | DIN rail module, split, detachable |
| Surge protection fault alarm | Vision, Multi-Stage |
| insulation characteristics | |
| Overvoltage Category | III |
| pollution level | 2 |
| Rated voltage UN | 12V DC |
| Connection Mode | in-line connection |
| Flexible Wire Cross Section | 0.2 mm² ... 2.5 mm² |
| Rigid conductor cross section | 0.2 mm² ... 4 mm² |
| Attachable Guide Cross Section AWG | 24 ... 12 |
| Dimensional drawing | |
| width | 17.7mm |
| height | 109.3mm |
| depth | 77.5mm (7.5mm with DIN rail) |
| Horizontal stitch pitch | 1 Partition |
| color | black (RAL 9005) |
| black (RAL 9005) | |
| flame retardant rating to UL 94 | V0 |
| Shell Material | PA 6.6 |
| Mechanical parameters | |
| Open Side Panel | No |
| movement direction | Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-Earth Ground |
| Maximum continuous operating voltage UC | 15V DC |
| 10V AC | |
| Rated current | 600 mA (40°C) |
| UC, the effective working current IC | ≤ 100 & micro;A (per path) |
| Residual Flow IPE | ≤ 100 & micro;A (per path) |
| Nominal discharge current In(8/20) & micro;s (core-core) | 10 kA |
| Rated discharge current In(8/20)& micro;s (core-ground) | 10 kA |
| pulse discharge current Iimp(350) & micro;s (core-ground) | 2.5 kA |
| Total discharge current ITotal(8/20) µs | 20 kA |
| voltage protection level Up(core-core) | ≤ 90V (C1 - 1 kV / 500 A) |
| ≤ 145V (C2 - 10 kV / 5 kA) | |
| ≤ 40V (C3 - 25 A) | |
| ≤ 40V (C3 - 50 A) | |
| voltage protection level Up(Line-Ground) | ≤ 90V (C1 - 1 kV / 500 A) |
| ≤ 145V (C2 - 10 kV / 5 kA) | |
| ≤ 40V (C3 - 25 A) | |
| ≤ 40V (C3 - 50 A) |