Phoenix G 5/4-equipment terminal 2716046, equipment terminal, nominal working voltage: 500V, rated current: 32 A, connection quantity: 8, number of digits: 4, wiring method: screw connection, rated wiring capacity: 4mm2, cross section: 0.2 mm2 -4mm2, installation method: direct screw connection, color: gray

Product Type straight-through terminal
product series G
Bits 4
connection quantity 8
Rows 1
potential 4
insulation characteristics
Overvoltage Category III
pollution level 3

Rated surge voltage 6 kV
rated conditions 1.02W

the number of connections per layer 8
Rated cross section 4 mm²
thread M3
Tightening torque 0.6 ... 0.8 Nm
stripping length 8mm
plug gauge A3
connection meets standards IEC 60947-7-1
Rigid conductor cross section 0.2 mm² ... 4 mm²
cross section AWG 24 ... 12 (as amended by IEC standards)
Flexible Wire Cross Section 0.2 mm² ... 4 mm²
WIRE CROSS SECTION, FLEXIBLE [AWG] 24 ... 12 (as amended by IEC standards)
Flexible conductor cross-section (sleeve without plastic insulation) 0.25 mm² ... 4 mm²
flexible conductor cross-section (sleeve with plastic insulating tube) 0.25 mm² ... 2.5 mm²
2 wires of the same cross section, rigid wire 0.2 mm² ... 1.5 mm²
2 wires with the same cross section, flexible wire 0.2 mm² ... 1.5 mm²
2 wires with the same cross section, flexible, with sleeve but not plastic sleeve 0.25 mm² ... 1.5 mm²
2 wires with the same cross section, flexible, with TWIN sleeve and plastic sleeve 0.5 mm² ... 1 mm²
Nominal current 32 A
Maximum load current 32 A (when connecting a conductor with a cross-sectional area of 4 mm²)
Rated voltage 500V
Rated cross section 4 mm²

Dimensional drawing
width 38mm
height 22mm
depth 24mm
aperture 3.2mm

color gray (RAL 7042)
flame retardant rating, according to UL 94 V0
Insulation Material Group I
insulation material PA
Application of Static Insulation Materials at Low Temperature -60°C
insulating materials (DIN EN 60216-1(VDE 0304-21)) 130°C
Insulation Relative Temperature Index (Electrical, UL 746 B) 130°C
railway vehicles (DIN EN 45545-2) R22 HL 1 - HL 3
Fire protection of railway vehicles (DIN EN 45545-2) R23 HL 1 - HL 3
railway vehicles (DIN EN 45545-2) R24 HL 1 - HL 3
Fire protection of railway vehicles (DIN EN 45545-2) R26 HL 1 - HL 3
Thermal Release NFPA 130 (ASTM E 1354) 28 MJ/kg
Surface Flammability NFPA 130 (ASTM E 162) through
Smoke specific optical density NFPA 130 (ASTM E 662) through
Smoke Toxicity NFPA 130 (SMP 800C) through
2716703

Phoenix G 5/4-Device Terminal 2716046

Product Center