Phoenix UK 10-TWIN-PE-ground terminal 3001433, ground terminal, wiring method: screw connection, rated wiring capacity: 10mm2, cross section: 0.5 mm2 -16mm2, installation method: NS 35/7,5, NS 35/15, NS 32, color: yellow and green
Product Type |
Ground terminal |
connection quantity |
3 |
Rows |
2 |
insulation characteristics |
Overvoltage Category |
III |
pollution level |
3 |
Rated surge voltage |
8 kV |
rated conditions |
1.82W |
the number of connections per layer |
3 |
Rated cross section |
10 mm² |
1 Upper 1 2 Lower 1 |
thread |
M4 |
Considerations |
Note the ampacity of the DIN rail. |
Tightening torque |
1.5 ... 1.8 Nm |
stripping length |
11mm |
plug gauge |
A6 |
connection meets standards |
IEC 60947-7-2 |
Rigid conductor cross section |
0.5 mm² ... 16 mm² |
cross-section AWG |
20 ... 6 (as amended by IEC standards) |
Flexible Wire Cross Section |
0.5 mm² ... 10 mm² |
WIRE CROSS SECTION, FLEXIBLE [AWG] |
20 ... 8 (as amended by IEC standards) |
Flexible conductor cross-section (sleeve without plastic insulation) |
0.5 mm² ... 10 mm² |
flexible conductor cross-section (sleeve with plastic insulating tube) |
0.5 mm² ... 6 mm² |
Rated cross section |
10 mm² |
width |
10.2mm |
height |
56.5mm |
NS 32 Depth |
64mm |
NS 35/7,5 depth |
59mm |
NS 35/15 Depth |
66.5mm |
color |
green and yellow |
flame retardant rating, according to UL 94 |
V0 |
Insulation Material Group |
I |
insulation material |
PA |
Application of Static Insulation Materials at Low Temperature |
-60°C |
insulating materials (DIN EN 60216-1(VDE 0304-21)) |
130°C |
Insulation Relative Temperature Index (Electrical, UL 746 B) |
130°C |
railway vehicles (DIN EN 45545-2) R22 |
HL 1 - HL 3 |
Fire protection of railway vehicles (DIN EN 45545-2) R23 |
HL 1 - HL 3 |
railway vehicles (DIN EN 45545-2) R24 |
HL 1 - HL 3 |
Fire protection of railway vehicles (DIN EN 45545-2) R26 |
HL 1 - HL 3 |
Thermal Release NFPA 130 (ASTM E 1354) |
28 MJ/kg |
Surface Flammability NFPA 130 (ASTM E 162) |
through |
Smoke specific optical density NFPA 130 (ASTM E 662) |
through |
Smoke Toxicity NFPA 130 (SMP 800C) |
through |
Overview |
Terminal Installation |
1.5 Nm ... 1.8 Nm (PE feet with mounting screws, M4) |
Mechanical parameters |
Open Side Panel |
No |
Oscillation/Broadband Noise |
Specifications |
DIN EN 50155 (VDE 0115-200):2018-05 |
spectrum |
Class 2, Class B service life test, carried out on bogies |
frequency |
f1= 5Hz to f2= 250Hz |
ASD rating |
6.12 (m/s²)²/Hz |
acceleration |
3.12g |
Test cycle per axis |
5 h |
Test Direction |
X-, Y-and Z-axes |
Results |
has passed the test |