Phoenix PT 2X2-BE-Surge Protector-Base 2839208, the base is used to install the protection plug PT, used for the protection of 2 two-wire floating ground signal circuits, between 3-4(GND) and 9-10 With bridge pieces, installed on NS/7.5 and NS35/15 rails, shell thickness: 17.5mm
Product Type | basic elements |
Product Series | PLUGTRAB PT |
type | base element, DIN rail mounting |
Bits | 4 |
Surge protection fault alarm | None |
line pairs per module | 2 |
insulation characteristics | |
Overvoltage Category | III |
pollution level | 2 |
Rated voltage UN | 24V AC |
24V DC |
Connection Mode | screw connection |
thread | M3 |
Tightening torque | 0.5 Nm |
Flexible Wire Cross Section | 0.2 mm² ... 2.5 mm² |
Rigid conductor cross section | 0.2 mm² ... 4 mm² |
Attachable Guide Cross Section AWG | 24 ... 12 |
Dimensional drawing | |
width | 17.7mm |
height | 90mm |
depth | 51.5mm (7.5mm with DIN rail) |
Horizontal stitch pitch | 1 Partition |
color | black (RAL 9005) |
COPPER | |
flame retardant rating to UL 94 | V-0 |
Shell Material | PA 6.6 |
Mechanical parameters | |
Open Side Panel | No |
Maximum continuous voltage Uc | 40V DC |
28V AC | |
Rated current | 450 mA (45°C) |
the resistance of each path | 2.2 Ω ± 10% |
500 mA (T) |
environmental conditions | |
protection level | IP20 |
ambient temperature (operation) | -40°C ... 85°C |
ambient temperature (storage/transport) | -40°C ... 85°C |
elevation | ≤ 2000 m (amsl) |
electrical clearance and creepage distance | |
Standards/Regulations | VDE 0110-1 |
Standards/Specifications | IEC 61643-21 |
Considerations | 2000 + Corrigendum 2001 + A1:2008, Revised + A2:2012 |
Standards/Specifications | EN 61643-21 |
Considerations | 2001 + A1:2009 + A2:2013 |
Installation Type | DIN rail: 35mm |