Phoenix CB E1 24DC/6A S-C P-electronic equipment circuit breaker 2800926, electronic equipment protection switch, 1 position, active current limit, output and control input status, plug for the base.
Product Type | Equipment circuit breaker |
Product Series | CB E |
type | needle type |
Bits | 1 |
Channels | 1 |
insulation characteristics | |
pollution level | 2 |
Overview | |
Nominal operating voltage | 24V DC |
18V DC ... 30V DC | |
Rated current IN | 6 A |
Rated overvoltage | 0.5 kV |
Breaking method | E (Electronic) |
required spare fuse | not required, built-in intrinsic safety components |
dielectric strength | 30V DC max (load circuit) |
Active Current Limit | type 1.25 x IN |
Fuse | electronic |
closed-circuit current I0 | Typical 8 mA (when switched on) |
Typical 11 mA (with status output) | |
power consumption | 1.04W (normal operation) |
temperature attenuation | 5 A (at 50°C) |
MTBF (IEC 61709, SN 29500) | 8320000 h (at 80% load at 25°C) |
7410000 h (at 40°C, 80% load) | |
voltage drop | 130 mV (IN) |
fail-safe components | 10 A DC |
Contact Type | without electrical isolation |
Load Circuit | |
Downtime | 130 ms (see time/current characteristic curve) |
undervoltage shutdown | < 14V (type off) |
> 17V (type on) | |
Maximum capacitive load | 20000 µF |
impact suppression | Typical 2 ms |
auxiliary contact | |
Contact Type | Positive switch signal output |
Status Output | |
output voltage | 24V DC |
output current | Maximum 0.2 A (short-circuit protection) |
Connection Mode | pluggable |