Phoenix AXL F AI8 1F-Analog Module 2688064,Axioline F, Analog Input Module, Analog Input: 8,0V ... 5V,-5V ... 5V,0V ... 10V,-10V ... 10V,0 mA ... 20 mA,4 mA ... 20 mA,-20 mA ... 20 mA, Connection Technology: 2-Wire System, Local Bus Transmission Rate: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connector

width 53.6mm
height 126.1mm
depth 54mm
Notes on dimensional data using TH 35-7.5 rails (as EN60715).

Application Description
Application Description for industrial applications only

Axioline F Local Bus
interfaces 2
Connection Mode bus base module
transmission speed 100 Mbps

Module
Input Address Area 16 Byte
Output Address Area 0 Byte
the required parameter data 27 Byte
the required configuration data 6 Byte

simulation: overview
Enter Name Analog Input
Input Description differential inputs for individually selectable voltage and current
Input Quantity 8
A/D conversion time 2 µs
A/D Converter Resolution 16 bits
Connection Mode in-line connection
connection system 2 wire system
Notes on connection technology Shielded, Twisted Pair
current input signal 0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
input current 104 Ω (typical)
voltage input signal 0V ... 5V
-5V ... 5V
0V ... 10V
-10V ... 10V
input voltage 268 kΩ (typical)
data format IB IL,S7 Compatible
input filtering 30Hz, 12kHz and average generation (parameterizable)
filtering RFI Filter Passive TP First Command
cut-off frequency (3dB) 30Hz
12 kHz (fast mode)
Signal-to-ground common mode voltage range -50V DC ... 50V DC
measurement value expression 16 bits (15 bits + sign bit)
protection circuit input; suppression diode
current input; No;± 5.2V DC, max, Imax= 50 mA
voltage input; ± 30V DC, max.

Product Type I/O components
Product Series Axioline F
type Modular structure
Installation position any position (no temperature decay)
Scope of supply includes bus base module and Axioline F connector
insulation characteristics
Overvoltage Category II (IEC 60664-1,EN 60664-1)
pollution level 2 (IEC 60664-1,EN 60664-1)

rated conditions 2W
potential: Axioline F local bus (UBus) power supply
supply voltage 5V DC (via bus base module)
current consumption Maximum 130 mA (up to HW 05)
Maximum 60 mA (from HW06)
Typical 105 mA (up to HW 05)
Typical 45 mA (from HW06)
2688051

Phoenix AXL F AI8 1F-Analog Module 2688064

Product Center