Phoenix AXL F AI8 1F-Analog Module 2688064,Axioline F, Analog Input Module, Analog Input: 8,0V ... 5V,-5V ... 5V,0V ... 10V,-10V ... 10V,0 mA ... 20 mA,4 mA ... 20 mA,-20 mA ... 20 mA, Connection Technology: 2-Wire System, Local Bus Transmission Rate: 100 Mbps, degree of protection: IP20, including bus base module and Axioline F connector
width
53.6mm
height
126.1mm
depth
54mm
Notes on dimensional data
using TH 35-7.5 rails (as EN60715).
Application Description
Application Description
for industrial applications only
Axioline F Local Bus
interfaces
2
Connection Mode
bus base module
transmission speed
100 Mbps
Module
Input Address Area
16 Byte
Output Address Area
0 Byte
the required parameter data
27 Byte
the required configuration data
6 Byte
simulation: overview
Enter Name
Analog Input
Input Description
differential inputs for individually selectable voltage and current
Input Quantity
8
A/D conversion time
2 µs
A/D Converter Resolution
16 bits
Connection Mode
in-line connection
connection system
2 wire system
Notes on connection technology
Shielded, Twisted Pair
current input signal
0 mA ... 20 mA
4 mA ... 20 mA
-20 mA ... 20 mA
input current
104 Ω (typical)
voltage input signal
0V ... 5V
-5V ... 5V
0V ... 10V
-10V ... 10V
input voltage
268 kΩ (typical)
data format
IB IL,S7 Compatible
input filtering
30Hz, 12kHz and average generation (parameterizable)
filtering
RFI Filter Passive TP First Command
cut-off frequency (3dB)
30Hz
12 kHz (fast mode)
Signal-to-ground common mode voltage range
-50V DC ... 50V DC
measurement value expression
16 bits (15 bits + sign bit)
protection circuit
input; suppression diode
current input; No;± 5.2V DC, max, Imax= 50 mA
voltage input; ± 30V DC, max.
Product Type
I/O components
Product Series
Axioline F
type
Modular structure
Installation position
any position (no temperature decay)
Scope of supply
includes bus base module and Axioline F connector
insulation characteristics
Overvoltage Category
II (IEC 60664-1,EN 60664-1)
pollution level
2 (IEC 60664-1,EN 60664-1)
rated conditions
2W
potential: Axioline F local bus (UBus) power supply