Phoenix DIKD 1,5-starter/actuator terminal 2715979, starter/actuator terminal, nominal working voltage: 250V, rated current: 24 A, wiring method: screw connection, 1st, 2nd and 3rd layer, rated wiring capacity: 2.5 mm2, cross section: 0.2 mm2 -4mm2, installation method: NS 35/7,5, NS 35/15, color: gray

Product Type Sensor/Actuator Terminal
connection quantity 6
Rows 3
potential 3
insulation characteristics
Overvoltage Category III
pollution level 3

Rated surge voltage 4 kV
rated conditions 0.77W

the number of connections per layer 2
Rated cross section 2.5 mm²
1st, 2nd and 3rd floors
thread M3
Tightening torque 0.5 ... 0.6 Nm
stripping length 8mm
plug gauge A3
connection meets standards IEC 60947-7-1
Rigid conductor cross section 0.2 mm² ... 4 mm²
cross-section AWG 24 ... 12 (as amended by IEC standards)
Flexible Wire Cross Section 0.2 mm² ... 2.5 mm²
WIRE CROSS SECTION, FLEXIBLE [AWG] 24 ... 14 (as amended by IEC standards)
Flexible conductor cross-section (sleeve without plastic insulation) 0.25 mm² ... 2.5 mm²
flexible conductor cross-section (sleeve with plastic insulating tube) 0.25 mm² ... 2.5 mm²
wiring capacity including plug-in bridges, rigid 4 mm²
wiring capacity including plug-in bridges, flexible 2.5 mm²
2 wires of the same cross section, rigid wire 0.2 mm² ... 1 mm²
2 wires with the same cross section, flexible wire 0.2 mm² ... 1 mm²
2 wires with the same cross section, flexible, with sleeve but not plastic sleeve 0.25 mm² ... 1 mm²
2 wires with the same cross section, flexible, with TWIN sleeve and plastic sleeve 0.5 mm² ... 1 mm²
Nominal current 24 A
Maximum load current 30 A (when connecting a conductor with a cross-sectional area of 4 mm²)
Rated voltage 250V
Rated cross section 2.5 mm²

width 6.2mm
height 72.5mm
NS 35/7,5 depth 54.5mm
NS 35/15 Depth 62mm

color gray (RAL 7042)
flame retardant rating, according to UL 94 V2
Insulation Material Group I
insulation material PA
Application of Static Insulation Materials at Low Temperature -40°C
insulating materials (DIN EN 60216-1(VDE 0304-21)) 125°C
Insulation Relative Temperature Index (Electrical, UL 746 B) 125°C

Surge Voltage Test
Results has passed the test
temperature rise test
Temperature rise requirement test temperature rise ≤ 45 K
Results has passed the test
Short-time withstand current 2.5 mm² 0.3 kA
0.3 kA
0.3 kA
Results has passed the test
Power frequency withstand voltage
Test voltage setpoint 1.5 kV
Results has passed the test
2715092

Phoenix DIKD 1,5-Starter/Actuator Terminal Block 2715979

Product Center

PRODUCT CENTER