Phoenix DT-LAN-CAT. 6-Surge protector 2881007,EA level (CAT6A) surge protection device, suitable for Gigabit Ethernet (up to 10 Gbps), Token Ring, FDDI/CDDI,ISDN and DS1. Suitable for Power over Ethernet (PoE / 4PPoE) "Mode A" and "Mode B". The RJ45 connection plug has a separate grounding cable and can be connected to the NS 35 DIN rail for grounding.
| Product Type | Information Technology |
| Product Series | DATATRAB |
| IEC Category | B2 |
| C1 | |
| C2 | |
| C3 | |
| D1 | |
| type | adapter for DIN rail mounting |
| Bits | 8 |
| line pairs per module | 4 |
| insulation characteristics | |
| Overvoltage Category | II |
| pollution level | 2 |
| Connection Mode | RJ45 |
| Dimensional drawing | |
| width | 25mm |
| height | 102mm |
| depth | 63.5mm |
| color | silver |
| black (RAL 9005) | |
| Shell Material | zinc die casting |
| Mechanical parameters | |
| Open Side Panel | No |
| movement direction | Line-Line & Line-Ground/Shield |
| Maximum continuous voltage UC(line-line) | ≤ 3.3V DC (±60V DC / PoE) |
| Rated current | ≤ 1.5 A (25 °C) |
| UC, the effective working current IC | ≤ 1 µA |
| Residual Flow IPE | ≤ 400 µA |
| Nominal discharge current In(8/20) & micro;s (core-core) | 100 A |
| Rated discharge current In(8/20)& micro;s (core-ground) | 2 kA (per pair of signal lines) |
| pulse discharge current Iimp(350) & micro;s (core-ground) | 1 kA |
| Total discharge current Itotal(8/20) µs | 10 kA |
| rated power pulse current lan (700)& micro;s (core-core) | ≤ 40 A |
| rated power pulse current lan (700)& micro;s (core-ground) | ≤ 160 A |
| Output voltage limit 1 kV/& micro;s (core-to-core) peak | ≤ 85V (PoE) |
| Output voltage limit 1 kV/& micro;s (core-ground) peak | ≤ 700V |
| Output voltage limit 1 kV/& micro;s (core-core) static | ≤ 9V |
| Output voltage limit 1 kV/& micro;s (core-ground) static | ≤ 700V |
| Residual voltage ln,(wire-wire) | ≤ 15V |
| ≤ 100V (PoE) | |
| voltage protection level Up(core-core) | ≤ 9V (B2 - 1 kV / 25 A) |
| ≤ 100V (B2 - 1 kV / 25 A - PoE) | |
| ≤ 12V (C3 - 20 A) | |
| voltage protection level Up(line-ground) | ≤ 900V (B2 - 4 kV / 100 A) |
| ≤ 700V (C2 - 4 kV / 2 kA) | |
| ≤ 1 kV (C3 - 80 A) | |
| response time tA(core-core) | ≤ 1 ns |
| response time tA (core-ground) | ≤ 100 ns |
| input attenuation AE, symmetric. | ≤ 1 dB (up to 100 Mz/direct measurement) |