Phoenix QUINT4-PS/1AC/24DC/2.5/PT-power 2909576, primary switching power supply QUINT POWER, in-line connection, DIN rail installation, input: 1 phase, output: 24V DC/2.5 A

AC operation
Input Voltage Range 100V AC ... 240V AC -15 % ... +10%
maximum dielectric strength 300V AC 30 s
National Grid Typical Voltage 120V AC
230V AC
Supply Voltage AC/DC
Impulse current Typical 10 A (at 25°C)
impulse current integral (I2t) < 0.1 A2s
Surge current limit 4.3 A (after 1 ms)
< 10 A
frequency range (fN) 50Hz ... 60Hz-10%... + 10%
grid buffer time Typical 54 ms (120V AC)
Typical 54 ms (230V AC)
power consumption 0.85 A (100V AC)
0.7 A (120V AC)
0.39 A (230V AC)
0.37 A (240V AC)
Rated power consumption 71 VA
protection circuit transient surge protection; varistor
Typical Response Time 500 ms
input fuse 3.15 A (slow fuse, internal)
PE discharge current < 0.25 mA (264V AC,60 Hz)
0.22 mA (264V AC,60 Hz)
DC operation
Input Voltage Range 110V DC ... 250V DC -20 % ... +40%
Supply Voltage AC/DC
power consumption 0.75 A (110V DC)
0.33 A (250V DC)

efficiency Typical 91.9 % (120V AC)
Typical 92.6 % (230V AC)
output characteristics U/ I Advanced
Rated output voltage 24V DC
output voltage (USet) setting range 24V DC ... 28V DC (constant capacity)
Rated output current (IN) 2.5 A
Static Boost (IStat.Boost) 3.125 A (≤ 40 °C)
Dynamic Boost (IDyn.Boost) 5 A (≤60°C (5 s), Input <150V AC Derating 0.5 %/V)
Attenuation > 60°C (2.5 %/K)
feedback voltage resistance ≤ 35V DC
output ≤ 32V DC
control deviation < 0.5 % (static load change 10% ... 90%)
<2% (dynamic load change 10% ... 90%,(10Hz))
< 0.1 % (input voltage variation is ± 10 %)
residual wave < 40 mVSS(rated value)
Short-circuit protection is
Anti-aircraft turn is
output power 60W
75W
120W
maximum no-load power consumption < 1W (230V AC)
2904598

Phoenix QUINT4-PS/1AC/24DC/2.5/PT-Power 2909576

Product Center