Phoenix QUINT4-PS/1AC/24DC/40/-power supply 2904618, primary switched QUINT POWER power supply for DIN rail installation, with optional output characteristic curve and SFB (selective fusing), protective coating and built-in decoupling MOSFET, input: 1 phase, output: 24V DC/40 A
Control Input (Configurable) Rem
output power ON/OFF (SLEEP MODE)
Default (Value)
Output power ON (>40 kΩ/24V DC/Open bridge between Rem and SGND)
AC operation
Network Type
star network
Rated input voltage range
100V AC ... 240V AC
Input Voltage Range
100V AC ... 240V AC -15 % ... +10%
Attenuation
< 100V AC (1 %/V)
maximum dielectric strength
300V AC 60 s
National Grid Typical Voltage
120V AC
230V AC
Supply Voltage
AC
Impulse current
Typical 12 A (at 25°C)
impulse current integral (I2t)
< 0.3 A2s
Surge current limit
12 A (after 1 ms)
AC frequency range
50Hz ... 60Hz-10%... + 10%
frequency range (fN)
50Hz ... 60Hz-10%... + 10%
16.7Hz (in accordance with EN 50163)
grid buffer time
Typical 27 ms (120V AC)
Typical 27 ms (230V AC)
power consumption
13.6 A (100V AC)
9.9 A (120V AC)
5.4 A (230V AC)
5.4 A (240V AC)
Rated power consumption
1072 VA
protection circuit
transient surge protection; varistor, gas discharge tube
Suction time
< 1 s
Typical Response Time
300 ms (from SLEEP MODE)
input fuse
16 A (slow fuse, internal)
recommend use
16 A ... 20 A (characteristics B, C, D, K or similar)
PE discharge current
< 3.5 mA
1.7 mA (264V AC,60 Hz)
DC operation
Rated input voltage range
110V DC ... 250V DC
Input Voltage Range
110V DC ... 250V DC -18 % ... +40%
Attenuation
< 110V DC (1 %/V)
Supply Voltage
DC
power consumption
12 A (110V DC)
5 A (250V DC)
efficiency
Typical 94.7 % (120V AC)
Typical 95.7 % (230V AC)
output characteristics
U/ I Advanced
Smart HICCUP
FUSE MODE
Rated output voltage
24V DC
output voltage (USet) setting range
24V DC ... 28V DC (constant capacity)
Rated output current (IN)
40 A
Static Boost (IStat.Boost)
45 A
Dynamic Boost (IDyn.Boost)
60 A (5 s)
selective fusing (ISFB)
215 A (15 ms)
Type of thermal magnetic circuit breaker
A1...A40 / B2...B25 / C1...C13 / Z1...Z16
Attenuation
> 60°C ... 70°C (2.5 %/K)
feedback voltage resistance
≤ 35V DC
output