Phoenix QUINT4-PS/24DC/24DC/20/SC/-DC/DC converter 1046881, primary switching DC/DC converter, QUINT POWER, DIN rail installation, SFB Technology (Selective Fuse Breaking), input: 24V DC, Output: 24V DC / 20 A
| Rated input voltage range |
24V DC |
| Input Voltage Range |
24V DC -25 % ... +40% |
| Wide Input |
No |
| maximum dielectric strength |
35V DC (60 seconds) |
| Impulse current |
Typical 2.7 A |
| impulse current integral (I2t) |
< 0.2 A2s |
| Surge current limit |
2.7 A (after 1 ms) |
| grid buffer time |
Typical 16 ms (24V DC) |
| power consumption |
27 A (24V DC) |
| Typical Response Time |
300 ms (from SLEEP MODE) |
| Suction time |
< 1 s |
| recommend use |
50 A (characteristics B, C or similar) |
| efficiency |
Typical 94.7 % (24V DC) |
| output characteristics |
U/ I Advanced |
| Smart HICCUP |
| FUSE MODE |
| Rated output voltage |
24V DC |
| output voltage (USet) setting range |
24V DC ... 28V DC (> 24V DC, continuous capacity) |
| Rated output current (IN) |
20 A |
| Static Boost (IStat.Boost) |
25 A |
| Dynamic Boost (IDyn.Boost) |
30 A (5 s) |
| selective fusing (ISFB) |
120 A (15 ms) |
| Type of thermal magnetic circuit breaker |
A1...A16 / B2...B13 / C1...C6 / Z1...Z16 |
| Short-circuit protection |
is |
| Anti-aircraft turn |
is |
| output power (PN) |
480W |
| output power (PStatic Margin) |
600W |
| output power (Pdynamic margin) |
720W (5 s) |
| feedback voltage resistance |
≤ 35V DC |
| output |
≤ 30V DC |
| residual wave |
< 50 mVSS |
| control deviation static |
<3% (load change, static 10%... 90%) |
| control deviation dynamics |
<3% (load change, static 10%... 90%) |
| Control Deviation Input Voltage Change |
<3% (load change, static 10%... 90%) |
| rise time |
< 100 ms (UOUT(10%... 90%)) |
| Concatenation |
is |
| maximum no-load power consumption |
< 4W |
| Maximum rated load power loss |
< 26.6W |
| Power Consumption SLEEP MODE |
< 2W |
| and connect |
Yes, for redundancy and increased capacity |