| input voltage |
24V DC |
| Input Voltage Range |
18V DC ... 30V DC |
| maximum dielectric strength |
35V DC (reverse polarity protected) |
| Fuse Internal Input |
None |
| National Grid Typical Voltage |
24V DC |
| Supply Voltage |
DC |
| Impulse current |
≤ 9 A (≤ 4 ms) |
| prevents polarity reversal |
is |
| Fixed Backup Threshold |
22V DC |
| 30V DC |
| Dynamic Trigger Threshold |
> 1V / 100 ms |
| Suction time |
max. 3 s |
| battery operation (battery start) |
8 s |
| voltage drop, input/output |
0.5V DC |
| Current consumption IN(UN,IOUT= IN,Icharge= 0) |
40.1 A |
| Current consumption Imax(UN,IOUT= IStat.Boost,ICharge= max) |
51.2 A |
| Current consumption INo-Load(UN,IOUT= 0, Icharge= 0) |
50 mA |
| Current consumption Icharge(UN,IOUT= 0, Icharge= max) |
6.1 A |
| power consumption PN(UN,IOUT= IN,Icharge= 0) |
965W |
| power consumption Pmax(UN,IOUT= IStat.Boost,Icharge= max) |
1120W |
| power consumption PNo-Load(UN,IOUT= 0, Icharge= 0) |
1.3W |
| power consumption Pcharge(UN,IOUT= 0, Icharge= max) |
147W |
| Signal Status Bat.-Start |
| Wiring Identification |
3.8 (+) |
| channel |
DI (Digital Input) |
| Status |
Bat.-Mode |
| Status Condition |
Low Layer (30 ms) |
| Signal-Status Assignment |
low - active |
| reference potential |
3.9 (SGND, same as 1.2, 2.2, 4.2) |
| LED status indicator |
yellow (battery mode) |
| Signal Status PS Boost |
| Wiring Identification |
3.7 (+) |
| channel (configurable) |
DI (digital input) default, AI (analog input) |
| status (configurable) |
charging current decreases |
| Status Condition |
lower layer |
| Signal-Status Assignment |
low - active |
| Unit Signal |
I (mA) |
| reference potential |
3.9 (SGND, same as 1.2, 2.2, 4.2) |
| Signal Status Remote |
| Wiring Identification |
3.6 (+) |
| channel |
DI (Digital Input) |
| status (configurable) |
Breaking |
| Status Condition |
lower layer |
| Signal-Status Assignment |
low - active |
| reference potential |
3.9 (SGND, same as 1.2, 2.2, 4.2) |
| LED status indicator |
green light, flashing (DC OK) |