Phoenix QUINT4-UPS/24DC/24DC/5-uninterruptible power supply 2906990,QUINT UPS, IQ Technology, DIN rail mounting, screw connection, input: 24V DC, output: 24V DC/5 A, charging current: 1.5 A
| input voltage | 24V DC |
| Input Voltage Range | 18V DC ... 30V DC |
| maximum dielectric strength | 35V DC (reverse polarity protected) |
| Fuse Internal Input | None |
| National Grid Typical Voltage | 24V DC |
| Supply Voltage | DC |
| Impulse current | ≤ 7 A (≤ 4 ms) |
| prevents polarity reversal | is |
| Fixed Backup Threshold | 22V DC |
| 30V DC | |
| Dynamic Trigger Threshold | > 1V / 100 ms |
| Suction time | max. 3 s |
| battery operation (battery start) | 8 s |
| voltage drop, input/output | 0.3V DC |
| Current consumption IN(UN,IOUT= IN,Icharge= 0) | 5.1 A |
| Current consumption Imax(UN,IOUT= IStat.Boost,ICharge= max) | 8.3 A |
| Current consumption INo-Load(UN,IOUT= 0, Icharge= 0) | 45 mA |
| Current consumption Icharge(UN,IOUT= 0, Icharge= max) | 1.8 A |
| power consumption PN(UN,IOUT= IN,Icharge= 0) | 121W |
| power consumption Pmax(UN,IOUT= IStat.Boost,Icharge= max) | 211W |
| power consumption PNo-Load(UN,IOUT= 0, Icharge= 0) | 1.1W |
| power consumption Pcharge(UN,IOUT= 0, Icharge= max) | 43W |
| Signal Status Bat.-Start | |
| Wiring Identification | 3.8 ( ) |
| channel | DI (Digital Input) |
| Status | Bat.-Mode |
| Status Condition | Low Layer (30 ms) |
| low signal | input connected to SGNd (3.9) or Bat |
| High Signal | input not connected or connected to> UBatConnection |
| Signal-Status Assignment | low - active |
| reference potential | 3.9 (SGND, same as 1.2, 2.2, 4.2) |
| LED status indicator | yellow (battery mode) |
| Signal Status PS Boost | |
| Wiring Identification | 3.7 ( ) |
| channel (configurable) | DI (digital input) default, AI (analog input) |
| status (configurable) | charging current decreases |
| Status Condition | lower layer |
| low signal | input connected or not connected to SGNd (3.9), <5V DC |
| High Signal | input has been connected to 13V DC... 30V DC connection |
| Signal-Status Assignment | low - active |
| simulation | 4 mA ... 20 mA (offset zero) |
| Unit Signal | I (mA) |
| load | 390 Ω |
| reference potential | 3.9 (SGND, same as 1.2, 2.2, 4.2) |
| Signal Status Remote | |
| Wiring Identification | 3.6 ( ) |
| channel | DI (Digital Input) |
| status (configurable) | Breaking |
| Status Condition | lower layer |