Phoenix QUINT-ORING/24DC/2X10/1X20-Redundant module, with protective coating 2320173, active QUINT redundant module for DIN rail installation, using ACB (automatic current equalization) technology and monitoring function, input: 24V DC, Output: 24V DC/2 x 10 A or 1 x 20 A, including installed universal DIN rail adapter UTA 107/30

DC operation
Rated input voltage range 24V DC
Input Voltage Range 18V DC ... 28V DC (SELV)
DC input voltage range 18V DC ... 28V DC (SELV)
Supply Voltage DC
prevents polarity reversal <is 60V
Rated input current (IN) 2x 10 A (-25°C ... 60 °C)
1x 20 A (-25°C ... 60 °C)
Maximum current Imax 2x 15 A (-25°C ... 40 °C)
1x 30 A (-25°C ... 40 °C)
1x 120 A (12 ms, SFB technology)
Transient overvoltage protection varistor
voltage drop, input/output 0.1V (IOUT= 20 A)

efficiency > 98%
Rated output voltage UIn- 0.1V
Rated output current (IN) 20 A (increased power)
10 A (redundant)
Static Boost (IStat.Boost) 1x 30 A
Dynamic Boost (IDyn.Boost) 1x 40 A (5 s)
selective fusing (ISFB) 1x 120 A (12 ms)
Attenuation 60°C ... 70°C (2.5 %/K)
output < 32V DC
Maximum rated load power loss 2W (IOUT= 20 A)
Concatenation No
signal: redundant OK ,13/14
Output Description Combination contact
maximum switching voltage Max. 30V AC/DC
Maximum starting current ≤ 100 mA (short-circuit protection)
signal: ACB (automatic current balance) OK, 23/24
Output Description contact closure: & Delta; UIN≤ 300 mV
maximum switching voltage Max. 30V AC/DC
Maximum starting current ≤ 100 mA (short-circuit protection)

Input
Connection Mode screw connection
Minimum cross section of rigid conductor 0.2 mm²
Maximum cross section of rigid conductor 4 mm²
Minimum cross section of flexible lead 0.2 mm²
Flexible lead maximum cross section 2.5 mm²
Minimum Wire Cross Section AWG 24
Maximum conductor cross section AWG 12
stripping length 8mm
thread M3
Minimum tightening torque 0.5 Nm
Maximum tightening torque 0.6 Nm
2320173