Phoenix QUINT-PS/1AC/24DC/ 5/CO-power supply, with protective coating 2320908, primary switching power supply QUINT POWER, screw connection, DIN rail installation, SFB Technology (Selective Fuse Breaking), input: 1 phase, Output: 24V DC/5 A

AC operation
Rated input voltage range 100V AC ... 240V AC
110V DC ... 250V DC
Input Voltage Range 85V AC ... 264V AC
90V DC ... 410V DC +5 % (UL 508: ≤ 250V DC)
AC input voltage range 85V AC ... 264V AC
DC input voltage range 90V DC ... 410V DC +5 % (UL 508: ≤ 250V DC)
maximum dielectric strength 300V AC
Supply Voltage AC/DC
Impulse current < 15 A
impulse current integral (I2t) < 1 A2s
AC frequency range 50Hz ... 60Hz
grid buffer time Typical 55 ms (120V AC)
Typical 55 ms (230V AC)
power consumption 1.5 A (100V AC)
0.6 A (240V AC)
1.2 A (120V AC)
0.6 A (230V AC)
1.3 A (110V DC)
0.6 A (220V DC)
1.4 A (100V DC)
0.6 A (250V DC)
Rated power consumption 141 VA
protection circuit transient surge protection; varistor
Typical Response Time < 0.15 s
input fuse 5 A (slow fuse, internal)
Allowable Spare Fuses B6 B10 B16 AC:
recommend use 6 A ... 16 A (AC: characteristics B, C, D, K)
PE discharge current < 3.5 mA

efficiency 90% typical (230V AC)
Rated output voltage 24V DC ±1%
output voltage (USet) setting range 18V DC ... 29.5V DC (> 24V DC, continuous capacity)
Rated output current (IN) 5 A (-25°C ... 60 °C,UOUT= 24V DC)
POWER BOOST (IBoost) 7.5 A (-25°C ... 40°C constant, UOUT= 24V DC)
selective fusing (ISFB) 30 A (12 ms)
Type of thermal magnetic circuit breaker B2 / B4 / C2
Attenuation 60°C ... 70°C (2.5 %/K)
feedback voltage resistance ≤ 35V DC
output ≤ 32V DC
control deviation <1% (load change, static 10%... 90%)
<2% (change of load, dynamic 10%... 90%)
< 0.1 % (input voltage variation is ± 10 %)
residual wave < 40 mVSS(rated value)
output power 120W
maximum no-load power consumption 3W
Maximum rated load power loss 15W
rise time < 0.1 s (UOUT(10%... 90%))
2866750

Phoenix QUINT-PS/1AC/24DC/ 5/CO-power supply with protective coating 2320908