Phoenix QUINT-PS/3AC/24DC/20-power supply 2866792, primary switching power supply QUINT POWER, screw connection, SFB Technology (Selective Fuse Breaking), input: 3 phases, output: 24V DC/20 A

AC operation
Rated input voltage range 3x 400V AC ... 500V AC
Input Voltage Range 3x 320V AC ... 575V AC
2x 360V AC ... 575V AC
450V DC ... 800V DC
DC input voltage range 450V DC ... 800V DC
Supply Voltage AC/DC
Impulse current < 20 A (typical)
impulse current integral (I2t) < 3.2 A2s
AC frequency range 45Hz ... 65Hz
DC frequency range 0Hz
grid buffer time > 20 ms (400V AC)
> 30 ms (500V AC)
power consumption 3x 1.6 A (400V AC)
3x 1.3 A (500V AC)
0.9 A (600V DC)
Rated power consumption 783 VA
protection circuit transient surge protection; varistor, gas discharge tube
power factor (cos phi) 0.66
Typical Response Time < 0.16 s
Allowable Spare Fuses B6 B10 B16 AC:
Allowed DC Spare Fuses DC: Connect a suitable fuse
recommend use 6 A ... 16 A (AC: characteristics B, C, D, K)
PE discharge current < 3.5 mA

efficiency > 93% (at 400V AC and rated)
output characteristics U/ I
Rated output voltage 24V DC ±1%
output voltage (USet) setting range 18V DC ... 29.5V DC (> 24V DC, stable capacity limit)
Rated output current (IN) 20 A (-25°C ... 60 °C,UOUT= 24V DC)
POWER BOOST (IBoost) 26 A (-25°C ... 40°C constant, UOUT= 24V DC)
selective fusing (ISFB) 120 A (12 ms)
Type of thermal magnetic circuit breaker B2 / B4 / B6 / B10 / B16 / C2 / C4 / C6
Attenuation 60°C ... 70°C (2.5 %/K)
feedback voltage resistance Max 35V DC
output < 35V DC
control deviation <1% (load change, static 10%... 90%)
<3% (load change, dynamic 10%... 90%)
< 0.1 % (input voltage variation is ± 10 %)
residual wave < 40 mVSS(rated value)
output power 480W
peak switching voltage rated load < 40 mVSS(rated, 20MHz)
maximum no-load power consumption 11W
Maximum rated load power loss 40W
rise time < 0.05 s (UOUT(10%... 90%))
2866718

Phoenix QUINT-PS/3AC/24DC/20-Power 2866792

Product Center

PRODUCT CENTER