Phoenix QUINT-PS/96-110DC/24DC/CO-DC/DC converter, protective coating 2905012, wide-range input QUINT DC/DC converter for DIN rail installation, primary switching mode, using SFB technology (Selective fusing technology), input: 96-110V DC, output: 24V DC/10 A

DC operation
Rated input voltage range 96V DC ... 110V DC
Input Voltage Range 67.2V DC ... 154V DC
Wide Input is
DC input voltage range 67.2V DC ... 154V DC
Supply Voltage DC
Impulse current < 10 A (typical)
impulse current integral (I2t) 0.37 A2s
grid buffer time Typical 10 ms (96V DC)
power consumption 3.5 A (96V DC)
3.1 A (110V DC)
prevents polarity reversal ≤ 154V DC
protection circuit transient surge protection; varistor
input fuse 10 A 150V DC (built-in (equipment protection))

efficiency > 92 % (UIN96V DC / UOUT24V DC)
> 92 % (UIN110V DC / UOUT24V DC)
output characteristics U/ I
Rated output voltage 24V DC ±1%
output voltage (USet) setting range 18V DC ... 29.5V DC (> 24V DC, stable capacity limit)
Rated output current (IN) 10 A (-40°C ... 60 °C)
POWER BOOST (IBoost) 12.5 A (-40°C ... 40°C constant, UOUT= 24V DC)
selective fusing (ISFB) 60 A (12 ms)
Type of thermal magnetic circuit breaker B2 / B4 / B6
Attenuation 60°C ... 70°C (2.5 %/K)
feedback voltage resistance 35V DC
output < 35V DC
Maximum capacitive load Unlimited
Active Current Limit 18 A
control deviation <1% (load change, static 10%... 90%)
<2% (change of load, dynamic 10%... 90%)
< 0.1 % (input voltage variation is ± 10 %)
residual wave < 20 mVSS
Short-circuit protection is
output power 240W
peak switching voltage rated load < 10 mVSS(20 MHz)
maximum no-load power consumption 4W (UIN110V DC)
Maximum rated load power loss 22W (UIN110V DC)
rise time < 2 ms (UOUT(10%... 90%))
and connect Yes, for redundancy and increased capacity
Concatenation is
signal: DC OK active
Output Description UOUT>0.9xUN: High Signal
Switching voltage range 18V DC ... 24V DC
Maximum starting current < 20 mA (short circuit protection)
signal: POWER BOOST, active
Output Description IOUTN: High signal
Switching voltage range 18V DC ... 24V DC
Maximum starting current < 20 mA (short circuit protection)
signal: UINOK, activate
Output Description UIN> 19.2V: high signal
Switching voltage range 18V DC ... 24V DC
Maximum starting current ≤ 20 mA (short-circuit protection)
signal: DC OK floating point
Output Description relay
2866718

Phoenix QUINT-PS/96-110DC/24DC/10/CO-DC/DC converter, protective coating 2905012

Product Center