Phoenix MINI MCR-EX-SD-23-38-LFD-solenoid driver 1277116,Ex I-solenoid driver used to control the inherent safety solenoid valve in potentially explosive areas. No-load voltage: 23V DC, Current limit: 38 mA, Standard configuration, Line fault detection, Safety Integrity Level (SIL, IEC 61508): 3, Screw connection

Product Type Electromagnetic driver
Product Series MINI Analog Pro

Suction time < 50 ms
Line Monitoring Line Fault Detection
electrical isolation
Overvoltage Category II (≤ 5000 m)
pollution level 2 (≤ 5000 m)
electrically isolated input/power supply IEC/EN 61010-1
Standards/Regulations IEC/EN 61010-1
Rated insulation voltage 250Vrms
Test Voltage 2.5 kV AC (50 Hz, 60 s)
insulation Double/reinforced insulation
galvanically isolated output/power supply, input IEC/EN 61010-1
Standards/Regulations IEC/EN 61010-1
Rated insulation voltage 300Vrms
Test Voltage 2.5 kV AC (50 Hz, 60 s)
insulation Double/reinforced insulation
galvanically isolated output/input, power supply IEC/EN 60079-11
Standards/Regulations IEC/EN 60079-11
Rated insulation voltage 265Vrms
galvanically isolated output/input, power supply IEC/EN 60079-7
Standards/Regulations IEC/EN 60079-7
Rated insulation voltage 251Vrms
power supply
Rated supply voltage 24V DC
Supply Voltage Range 19.2V DC ... 30V DC (24V DC,-20 % ... +25 %)
power consumption < 1.5W

signals: logic
Input Number 1
toggle level "0" signal 0V DC ... 5V DC
Toggle level "1" signal 15V DC ... 30V DC
input current < 3 mA
input impedance > 1 MΩ (high resistance in case of line fault at output)
Line Fault Detection < 25 Ω (short circuit)
> 10 k Ω (line break)
2902040

Phoenix MINI MCR-EX-SD-23-38-LFD-Electromagnetic Drive 1277116

Product Center

PRODUCT CENTER