Phoenix MINI MCR-SL-IDS-I-I-output isolation amplifier 2905577,3-terminal output signal isolation amplifier, used to send 0/4 ... 20 mA signals from the controller to the field load, simultaneous 3-terminal electrical isolation between input, output and power supply, using screw connection

Product Type Feeder Isolator
Product Series MINI Analog
Channels 1
insulation characteristics
Overvoltage Category II
pollution level 2

electrical isolation 3 End Isolation
cut-off frequency (3dB) > 175Hz
protection circuit transient protection
Signal Transmission Behavior In = Out
step response (10-90%) < 2 ms
maximum temperature coefficient < 0.01 %/K
temperature coefficient, typical < 0.01 %/K
Maximum transmission error ≤ 0.1 % (of terminal value)
Electrical isolation input/output/power supply
Rated insulation voltage 50V AC/DC
Test Voltage 1.5 kV AC (50 Hz, 60 s)
insulation foundation isolation conforming to IEC/EN 61010
Power
Rated supply voltage 24V DC
Supply Voltage Range 19.2V DC ... 30V DC (DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, order number 2869728) can be used to bridge the power supply. Can be stuck to a 35mm DIN rail conforming to the EN60715 standard))
power consumption < 600 mW (24V DC)

signal
Input Number 1
current input signal 0 mA ... 20 mA
4 mA ... 20 mA
Maximum current input signal 20 mA
Input Voltage Limit < 2V (20 mA)

signals: current
outputs 1
current output signal 0 mA ... 20 mA
4 mA ... 20 mA
load/output load current output ≤ 800 Ω (when 20 mA)
fluctuation < 20 mVrms
2864422

Phoenix MINI MCR-SL-IDS-I-I-Output Isolation Amplifier 2905577

Product Center