Phoenix MINI MCR-SL-RPSS-I-I-feed isolator 2864079,MCR repeater power supply, HART transparent, input signal: 4 mA ... 20 mA, output signal: 4 mA ... 20 mA, screw connection
Product Type
Feeder Isolator
Product Series
MINI Analog
Channels
1
insulation characteristics
Overvoltage Category
II
pollution level
2
electrical isolation
3 End Isolation
galvanic isolation between input and output
is
cut-off frequency (3dB)
175Hz (typical)
rated conditions
700 mW (24V DC)
400 mW (24V DC)
protection circuit
transient protection
Signal Transmission Behavior
In = Out
step response (10-90%)
< 2 ms
maximum temperature coefficient
< 0.005 %/K
temperature coefficient, typical
< 0.002 %/K
Maximum transmission error
≤ 0.2 % (of terminal value)
Typical transmission error
≤ 0.1 % (of terminal value)
Electrical isolation input/output/power supply
Rated insulation voltage
50V AC/DC
Test Voltage
1.5 kV AC (50 Hz, 60 s)
insulation
foundation isolation conforming to IEC/EN 61010
power supply
Rated supply voltage
24V DC
Supply Voltage Range
20.4V DC ... 30V DC (DIN rail bus connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, order number 2869728) can be used to bridge the power supply. Can be stuck to a 35mm DIN rail conforming to the EN60715 standard))
power consumption
< 900 mW (24VDC, feeder isolator operation)
< 600 mW (24VDC, isolator operation)
signals: current
Input Description
sensor circuit
Input Number
1
current input signal
0 mA ... 20 mA (Isolator operation)
4 mA ... 20 mA (feeder isolator and isolator operation)
Maximum current input signal
28 mA
input current
approx. 50 Ω
Transmitter supply voltage
16.5V