Phoenix MACX MCR-IDS-I-I-output isolation amplifier 2908063, output signal isolation transmitter, HART transparent. Isolate and transmit the 0/4 mA ... 20 mA signal to the load in the safe area. 3-terminal electrical isolation, line fault detection (can be turned off by DIP switch), SIL 2 (SC3) in accordance with IEC 61508, screw connection.
| Product Type | Output Isolation Amplifier |
| Product Series | MACX Analog |
| Channels | 1 |
| Model | Isolation Amplifier with SIL Functional Safety |
| configuration | DIP switch |
| Function | |
| configuration | DIP switch |
| electrical isolation | 3 End Isolation |
| signal transmission behavior | In = Out |
| step response (10-90%) | < 140 & micro;s (for jumpers 4 mA ... 20 mA) |
| maximum temperature coefficient | 0.01 %/K |
| temperature coefficient, typical | ≤ 0.005 %/K |
| Maximum transmission error | 0.1 % (final value 20 mA) |
| Typical transmission error | ≤ 0.05 % (final value 20 mA) |
| electrical isolation | |
| Overvoltage Category | II |
| pollution level | 2 |
| electrical isolation input/output IEC/EN 61010-1 | |
| Standards/Regulations | IEC/EN 61010-1 |
| Rated insulation voltage | 300Vrms |
| Test Voltage | 2.5 kV AC (50 Hz, 60 s) |
| insulation | security isolation |
| electrically isolated input/power supply IEC/EN 61010-1 | |
| Standards/Regulations | IEC/EN 61010-1 |
| Rated insulation voltage | 50Vrms |
| Test Voltage | 1.5 kV AC (50 Hz, 60 s) |
| insulation | Foundation Isolation |
| galvanically isolated output/power supply IEC/EN 61010-1 | |
| Standards/Regulations | IEC/EN 61010-1 |
| Rated insulation voltage | 300Vrms |
| Test Voltage | 2.5 kV AC (50 Hz, 60 s) |
| insulation | security isolation |
| power supply | |
| Rated supply voltage | 24V DC -20 % ... +25% |
| Supply Voltage Range | 19.2V DC ... 30V DC |
| Maximum current consumption | < 45 mA (24V DC / 20 mA) |
| power consumption | < 0.8W (24V DC / 20 mA) |
| power consumption | ≤ 1.1W (24V DC / 20 mA) |
| signals: current | |
| current input signal | 0 mA ... 20 mA (function (short-circuit detection off)) |
| 0.2 mA ... 20 mA (function (short-circuit detection start)) | |
| 4 mA ... 20 mA (safe) | |
| 0 mA ... 24 mA (undervoltage/overvoltage signal range) | |
| input current | ≤ 30 mA |
| input impedance | > 1 MΩ (in case of line fault) |
| Line Fault Detection | > 0.2 mA (Input Current Response Threshold) |
| voltage drop | < 2.4V (at 20 mA) |